Installing the Gas Fireplace  

manufacturer) to ensure that adequate combustion air is 
provided  for  proper  function  of  this  fireplace.  Fireplaces  
take  up  a  large  volume  of  replacement  air  from  outside  
the  house  and  if  the  house  is  of  airtight  construction,  
smoke spillage may occur if proper draft is not achieved. 

4)  There  are  many  conditions  beyond  a  manufacturer

’s  

 

control  regarding  improper  fireplace  operation.  The 
manufacturer  cannot  ensure 

“smoke  free”  operation,  

nor  can  the  manufacturer  take  on  the  responsibility  
for  problems  with  surrounding  construction;  chimneys  
that  have  not  been  built  at  the  right  heights;    system  
drafts  caused  by  faulty  mechanical  systems;  adverse  
weather  conditions  or  any  other  inclement  environmental  
situations over which the manufacturer has no control. 

5)  Inspect  all  fireplace  &  chimney  components  for  evidence  
 

of damage prior to starting installation. Consult your local 
distributor for replacement parts if necessary. 

6) Under   no   circumstances   should   you   make   any   
 

adjustments or modifications to the chimney system 
during  the  installation  procedure.  If  you  do,  you  are  not  
only  liable  for  negating  the  warranty,  but  you  could  very  
well  cause  a  serious  malfunction  of  the  fireplace.  You  
must follow your  chimney manufacturer

’s instructions. 

 

Fireplace Heights 

When  installed,  the  maximum  overall  height  of  the  

Chimney  System  is  40  feet.  The  minimum  installed  height  
of  the  completed  Chimney  System  is  14  feet  with  a  straight  
flue stack, 17 feet if the chimney  includes one or two  offset  
sections. 

Supporting Floor Systems 

It is the  ultimate responsibility  of the  installer to ensure that 
proper concrete slab supports are used. 
 

WARNING

    to    the    licensed    design    professional    and/or 

building contractor: It is  your responsibility to be certain  that 
the Mason-Lite can  be  properly supported by  the combustible 
floor system on which the fireplace will rest. 

 
 

Fig. 9-1 

For other than floor framing anchor rods, see 

For fireplace support foundations installed on concrete refer to 
Appendix I (page 18 ) for specific instructions. 

 
 

Fig. 9-2 

A35 

Brackets  
(16 req

’d) 

 
 
 
 
 
 
 
 
 

Example only 

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor  sheathing  
not  shown  for  
clarity 

 

Rebar locations 

Lay-out the position of  the fireplace and  drill  holes  where the 
rebars  will  be  located.  Secure  eight  #3  rebars  4  inches  into 
concrete foundation with ITW Epoxy or Simpson Epoxy. 

Follow  manufacturer

’s  instructions  for  installation  of  rebar 

into slab. 

 

Wood Floor 

 

Fig. 9-3  

I-Joist Anchoring 

Fig.  10-2  for  method  of  connecting  firebox 

rear wall anchors. 

48 3/4" 

 
8" 

 
12" 

top view 

 
 
 
 
 
 
 
 

Simpson  

strong-tie 

A-35  or  

equivalent 

 
 
 
 
 
 
 
 
 
 
 
 

Example only  

REV 1 - 0907231405 

L-A2-27509 

Содержание MGFPST-43

Страница 1: ...is fireplace must be connected to a working flue meeting the requirements of the ANSI Z21 50 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The installation including provisions for combustion ventilation air and required minimum permanent vent opening must c...

Страница 2: ... 15 16 16 16 16 16 17 17 17 18 19 19 19 20 20 20 20 20 20 21 21 22 22 22 22 22 22 23 23 23 23 23 23 Tested Listed By MFI 315 WEST 3RD ST SANTA ANA CA 92701 Industries LLC DATE OF MFG SERIAL No Report No TBD MODEL No MGFPST 43 GAS TYPE NG LP WARNING THIS FIREPLACE HAS BEEN TESTED FOR USE ONLY WITH APPROVED GLASS DOORS TO REDUCE THE RISK OF FIRE OR INJURY CONSULT OWNER S MANUAL THIS FIREPLACE IS DES...

Страница 3: ...ting plate MFPST43 MFP16 11 4 3 Rebar Ø 3 8 x 36 MFP49 11 10 2 Dome front rear upper MFSTP 43 10 12 9 1 Dome top for 16 class A chimney MFPST 43 9 8 8 2 Dome side upper MFPST 43 8 7 2 Dome side lower MFP 43 7 6 6 2 Lintel MFP 43 6 15 3A 1 Side wall w 4 knockout MFP 43 3A 3 7 Side wall MFP 43 3 3 11 1 3A Refractory Firebox Liners Herringbone Pattern shown Also available in Running Bond MFP43STSHBL ...

Страница 4: ...required up to header or top plate 1 2 MIN 0 MIN 57 I D FRAMING Fig 4 2 Framing dimensions 2 MIN 0 MIN 28 O D ZERO CLEARANCE TO COMBUSTIBLES BOTH SIDES AND BACK OF FIREPLACE WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury REV 1 0907231405 4 L A2 27509 ...

Страница 5: ...it 4 1 Damper clamp 5 1 Lava Rock qty of 4 6 1 Front bottom log 30 7 1 Front bottom log 30 8 1 Top log 18 9 1 Top log 18 10 1 Top log 20 11 1 Top log 17 6 7 1 8 11 2 4 5 Photos not to scale Contact Mason lite for replacement parts and accessories as listed in these parts lists 9 10 3 REV 1 0907231405 5 L A2 27509 ...

Страница 6: ...g code approvals and may cause property damage personal injury or loss of life The burner included with this gas fireplace is non convertible and only meant to be used with the gas listed on the rating plate Burner p n BTU x 1000 size top front Included in Nat LP MGFPST 43 P 90 23 45 44 55 MGFPST 43 Nominal BTU based on gas inlet pressure Nominal gas inlet pressure for natural gas is 5 W C Require...

Страница 7: ...ding sizing and suitability for the installation into this Enclosure prior to installation Statement of Intended Use The Mason Lite Masonry Fireplace is a modular refractory masonry unit designed for field assembly The firebox is constructed using pre cast interlocking refractory blocks The blocks are then secured to each other using Mortar The system includes all parts necessary for the assembly ...

Страница 8: ...allations Internal Wall Installation Island Installation Clearance to Combustibles The distance to be maintained from the surfaces of the fireplace to combustibles must be observed Below is a list of the most common combustible materials to name a few Drywall Wood flooring Plywood sub flooring Wood Framing Particle board Mill board Plywood paneling Maintain the following clearances Unit front side...

Страница 9: ...n of the fireplace You must follow your chimney manufacturer s instructions Fireplace Heights When installed the maximum overall height of the Chimney System is 40 feet The minimum installed height of the completed Chimney System is 14 feet with a straight flue stack 17 feet if the chimney includes one or two offset sections Supporting Floor Systems It is the ultimate responsibility of the install...

Страница 10: ...y the floor framing Additional floor joists or I joists may be required as determined by the licensed design professional The weights are noted in Table I for each MASON LITE unit model It is the task and responsibility of the general contractor installer to see that the proper reinforcement for weight loads are made by a licensed design professional prior to the fireplace installation As stated a...

Страница 11: ...Four or more fasteners to attach metal base to floor joists 4 Mason Lite Mortar at least one 50 lb bucket two for MFP63 Tools needed for both above installations 1 One 4 level 2 Roto hammer with drill bit needed for concrete slab install only 3 Drill motor with mixer blade to mix Mason Lite Mortar 4 Two empty 5 gallon buckets to mix Mason Lite Mortar 5 One wheelbarrow and shovel to mix concrete 6 ...

Страница 12: ...rebox side walls moving up keeping components moist mixing mortar as you need it and threading the mortar appropriately as you stack each section one onto the next Constantly check for squareness and levelness while building each course of block As you complete each section make certain that you adhere the mortar at each and every joint Fig 12 2 Setting Firebox sides Fig 12 3 Keep damp at all time...

Страница 13: ...ssembly 17 As you are connecting each MASON LITE component be certain you are following the instructions given previously for using MASON LITE mortar Stop to look at the smoke dome side front and rear walls to see that they are aligning correctly and that the surfaces be smooth and uniform Make sure connections are covered with an adequate amount of mortar Remember that you have the option of usin...

Страница 14: ...n Lite Firebrick Liners screws Existing Ceiling Frame framework to house the chimney system 22 Now that you have completed the smoke dome assembly all the components should stack up for a smooth transition into the flue components Setting the smoke dome completes the MASON LITE Firebox and Smoke Dome assembly You are now ready to begin the installation of the necessary firebrick lining and the flu...

Страница 15: ...ern the proper instructions from the fireplace liner manufacturer and also understand the type of adhesive or cement he is to use Make sure the fireplace is installed with the finished firebrick floor of the fireplace so that it is at least 11 eleven inches above the combustible floor system Disclaimer Masonry Fireplace Industries wishes to express that as the manufacturer of Mason Lite Fireplaces...

Страница 16: ...for outside combustible air It can go straight out through an outside wall or into a ventilated crawl space If crawl space is used check codes for proper termination 3 Be sure that you carefully check the source of the outside air before you choose the site for your air intake You don t want a place where snow will collect where bushes or trees will be growing or a location that is too close to an...

Страница 17: ...ling holes into damper plate 5 Attach damper chain stop on center rear of lintel 3 three inch vertical from opening using 3 8 cement fasteners Fig 17 1 Return Return Elbow Elbow Elbow Elbow when building the framework for the chimney system Fireplace Door Accessory IMPORTANT Only Crown Breckinridge or McKenzie Pendelton Doors are approved for use with this fireplace For installation Instructions s...

Страница 18: ...concrete slab The concrete strength and durability shall comply with Sections TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MINIMUM SPECIFIED COMPRESSIVE STRENGTH a f c TYPE OR LOCATION OF CONCRETE CONSTRUCTION Weathering Potential b Negligible Moderate Severe Basement walls foundations and other concrete not exposed to the weather 2 500 2 500 2 500C Basement slabs and interior s...

Страница 19: ...d female for the spill switch wires connection The short spill switch wire is to be routed across and into the top hole on the opposite side of the fireplace Connect the wire to the opposite baffle assembly Fig 19 1 Owner s Operation Precautions Installers of the Mason Lite are urged to call the attention of fireplace owners to the following precautions The installer should hand deliver this owner...

Страница 20: ...Pilot if neccessary 1 Follow the lighting instructions to light the pilot The pilot flame should encircle the generator tip which is preset at the factory Fig 20 2 Ordinarily the pilot will not require field adjustment 2 If adjustment is necessary remove the cap screw Fig 20 1 and turn the smaller gas adjustment screw inside counterclockwise to increase the pilot flame and clockwise to decrease th...

Страница 21: ...th the burner pipe Repeat for the second front log on the opposite side of the see thru burner 2 Place the top logs across the two bottom logs in the order and positions shown below Fig 21 1 Fig 21 2 8 9 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury 11 1...

Страница 22: ...ay lit see the Troubleshooting section Lighting and Extinguishing the Burner System To turn on your gas log set with the pilot lit turn the safety valve knob to the ON position Switch the toggle switch control to the on UP position and the gas log set will light To turn off your gas log set switch the toggle switch control to the off DOWN position The pilot will remain lit See the instructions tha...

Страница 23: ...No Gas to Burner 3 Fireplace Not burning properly 4 Fireplace will not shut OFF 5 Frequent pilot outage 6 Fireplace shuts down during operation 7 Excessive soot on logs CAUSE a Pilot generator may not be producing sufficient millivoltage b Pilot flame making a blowing sound c Generator wire leads attached to the wrong terminals on the valve d Defective thermomagnetic safety in valve a Safety valve...

Страница 24: ..._________ Orifice Other __________ Leak Test ___________ Burn Test ___________ Gas Type NAT PROPANE Date ___________ Model ___________ Serial ___________ Air Shutter ___________ Inspector ___________ REV 1 0907231405 24 L A2 27509 ...

Отзывы: