Output Range
Low (0%)
Low Range for Source Output.
Range:
Default Output Low to
Output Range High (100%)
This parameter is enabled, if
Main Display
in
MENU
→
DISPLAY
→
SOURCE
is set to
Percentage
or
Scaled.
Output Range
High (100%)
High Range for Source Output.
Range:
Output Range Low(0%)
to Default Output High
This parameter is enabled, if
Main Display
in
MENU
→
DISPLAY
→
SOURCE
is set to
Percentage
or
Scaled.
Scaled Output Range
Low (0%)
Scaling Low Range for Source Output.
Range:
-99999 to
Scaled Output Range High (100%)
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
→
DISPLAY
→
SOURCE
is set to
Scaled.
Scaled Output Range
High (100%)
Scaling High Range for Source Output
Range:
Scaled Output Range Low(0%)
to 99999
Decimal Point for this EditBox can be changeable.
This parameter is enabled, if
Main Display
in
MENU
→
DISPLAY
→
SOURCE
is set to
Scaled.
TF
(Transfer Function)
Transfer Function for Scaling
Available Options:
Linear
x^2 (x
2
)
x^(1/2) (
√x)
This parameter is enabled, if
Main Display
in
MENU
→
DISPLAY
→
SOURCE
is set to
Scaled.
Source Type
Source Output Format
Available Options:
STEP
RAMP
At a time one can be selectable.
Press F1 key on the one of the option for more settings.
Содержание PCE-MCA 50
Страница 74: ...5 2 Replacing the Battery 2 3 1...
Страница 85: ...6 17 Enclosure Dimensions All dimensions are in mm...