5.2 P
ROTECTION
A
GAINST
S
HORT
-
CIRCUITS
A
ND
O
VERLOAD
The generator is protected against short-circuits and
electrical overload.
A magnetothermal switch (ref.1) cuts off the electrical
current when a short-circuit occurs or when the current
delivered exceeds the rated value.
Before restoring the current delivery remove the
cause of the cut off, then disconnect the loads and
restore the magnetothermal switch on “ON”
position.
5.3 P
ROTECTION
A
GAINST
S
HORT
-
CIRCUITS
O
F
L
OW
-
VOLTAGE
E
LECTRICAL
S
YSTEM
.
The low voltage electric plant is protected by 2 thermal
switch (ref.2), they shutdown the generator set.
The first thermal switch stops the generator set, turns
off all the alarm light and prevents the starting.
The second thermal switch stops the generator set when
there is a stop electromagnet failure on the generator
set.
N.B. It does not prevent the START command, the alarm
lights are active. Press the thermal switch to restore the
contact.
5.4
F
USES
#
#
#
#
#
- Protection module fuse
On the printed circuit of the engine protection module
there is a fuse (ref.4) to protect the module. Remove
the frontal panel unscrewing the 4 screws (ref.5) to
enter in it.