Page 9
Commander UCP 5000 / 5100 Series
3.3.3 Custom PDUs
Custom PDUs may or may not have outlets which are not subject to the EPO system. The pattern of labeling outlets may
have to follow specific needs defined by the customer, so it may not be obvious which outlets will remain powered. The
end user will need to determine this based on knowing the original design requirements.
If the custom PDU has RCM software and switched outlets, then the behavior described above in
will apply. Please read that section for details.
If the custom PDU does not have RCM networking software with switched outlets, then any outlet designed to not react to
the EPO system will simply remain on (as long as the PDU is powered) even when the EPO button is pressed or the EPO
Mode switch on the PDU is the Off (middle) position.
3.4 Using Aux1/Aux2 Outlets
These two outlets are wired directly to the input power, and are always powered. They are not subject to the On/Off/EPO
controls of the UCP, nor are they subject to the front panel circuit breaker. The combined load of both outlets is subject to
the input power rating of the unit (see