Commander UCP 5000 / 5100 Series
2 Installation
2.1 Installation Notes
The following guidance must be followed for proper installation of the product.
1. Mounting: This product is designed for mounting in an EIA-310 compliant 19” rack. The user is responsible for
ensuring the mounting method provides adequate structural support for the product and any attached cables.
The user is also responsible for ensuring the mounting location provides adequate ventilation to dissipate heat
generated during operation of the product. Ensure the product is securely mounted before applying power.
2. Chassis ground: The rear of the chassis includes a redundant chassis ground screw and ground wire. If desired for
your installation location, connect the chassis ground wire to the rack cabinet using an appropriate fastener.
3.
This product includes a power cord with a plug, which is used to disconnect power to the product. The facility socket
outlet must be installed near the equipment and must be easily accessible.
4. Connect the appropriate remote control cables between the product and one or more PDUs.
5. Ensure the Control Breaker is in the reset (depressed) position.
6. Connect the product power cord to the facility socket outlet.
7. Facility Power Source: The facility power source for this product must include an overcurrent protective device with a
maximum rating as defined in the table below:
Main Inlet
Location
Continuous Current
Rating
Mains Protection
Required
NEMA 5-15P
United States
12A
15A
IEC C-13
United States
12A
15A
IEC C-13
European Union
10A
10A
The current rating for the input and output signals of the control connectors on the back panel is 4 Amps.
See the Specifications pages for full details on dimensions, connections, and ratings.