46
Marvair Wall Mount Heat Pump I&O Manual
11/2021 New
Cooling (Check and Record Readings)
After about 10 minutes of operating in the cooling mode, check and record the following data points.
Inside Temperature (IAT)
ºF
Outside Temperature (OAT)
ºF
Entering Condenser Air Temperature (Should be same temp as OAT)
ºF
Leaving Condenser Air Temperature (Acceptable Range 15º - 20º above OAT)
ºF
Return Air Temperature (RAT) db (Should be same temp as IAT)
ºF
Return Air Temperature (RAT) wb (used to calculate RH% of Return Air)
ºF
Supply Air Temperature (SAT) db (Acceptable Range 15º - 20º below RAT)
ºF
Return Air Temperature (SAT) wb (used to calculate RH% of Supply Air)
ºF
Compressor Amps (L1)
ºF
Compressor Amps (L2)
ºF
Compressor Amps (L3)
ºF
Cooling Stop
Adjust the cooling setpoint to approximately two degrees above the current indoor temperature. The
unit will sequence off, stop cooling.
Did the Compressor stop? .................................................................................................
❒
Yes
❒
No
Did the Condenser Fan (CFM) stop? ................................................................................
❒
Yes
❒
No
Did the indoor blower motor (IBM) Stop? .......................................................................
❒
Yes
❒
No
G.
Electric Reheat Mode
NOTE: If the HVAC system you are testing is not configured with Dehumidification Option, Skip this
section of the Start-up / Commissioning Checklist.
Has the Humidistat Control been installed & wired to the Dehumidification input? .......
❒
Yes
❒
No
Has the Humidistat Control been properly setup for dehumidification? ..........................
❒
Yes
❒
No
Adjust the cooling setpoint so there is No demand for cooling. Adjust the Humidity setpoint so there
is No demand for dehumidification. The unit will not be running.
Electric Reheat Start
Adjust the Humidity setpoint to approximately ten percent below the current indoor Humidity
(Humidistat display should indicate current RH%). After the short delay, the unit will sequence on,
start dehumidifying.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor On? ......................................................................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) On? (Ambient conditions may delay CFM) .......................
❒
Yes
❒
No
Is the Heater On? (Clamp an AmpProbe on one leg of the heater contactor to verify) ....
❒
Yes
❒
No
Electric Reheat Lock-Out
While the system is still operating in “Dehumidification Mode”. Activate Mechanical Cooling.
Do Not change the Humidity Setpoint on the Humidistat. Simply adjust the cooling setpoint to
approximately four degrees below the current indoor temperature. After the short delay, the unit will
sequence on, start cooling. Notice: system did not turn off. The Only change that occurred is “Heater
turned off”.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor On? ......................................................................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) On? .....................................................................................
❒
Yes
❒
No
Is the Heater Off? (Clamp an AmpProbe on one leg of the heater contactor to verify) ...
❒
Yes
❒
No