50
Marvair Wall Mount Heat Pump I&O Manual
11/2021 New
Three Phase Units
Heater kW = (HCAL1*L1&L2) + (HCAL2*L1&L3) + (HCAL3*L2&L3)/1000 = __________kW.
Example: (HCAL1*L1&L2) + (HCAL2*L1&L3) + (HCAL3*L2&L3)
1000
Measured Voltage: L1&L2 = 241 Volts
Measured Amperage: L1 = 8.28 Amps
1995.48
Measured Voltage: L1&L3 = 243 Volts
Measured Amperage: L1 = 8.22 Amps
1997.46
Measured Voltage: L1&L2 = 235 Volts
Measured Amperage: L1 = 8.57 Amps
2013.95
6006.89 / 1000 = 6.01kW (6kW)
Outdoor Thermostat Set Point ODT
Adjust the ODT setpoint to the temperature appropriate for your application (either “Auxiliary Heat”
or “Mechanical Heat Lockout”). If you need assistance selecting the proper temperature contact tour
HVAC system designer responsible for the application. After adjusting the ODT for your application,
the HVAC system will go back to Mechanical Cooling.
Note: The range of the Outdoor Thermostat is
0ºF to 50ºF.
Is the indoor blower motor (IBM) On? .............................................................................
❒
Yes
❒
No
Is the Compressor On? ......................................................................................................
❒
Yes
❒
No
Is the Condenser Fan (CFM) On? (Ambient conditions may be delay CFM) ..................
❒
Yes
❒
No
Is the Heater Off? (Clamp an AmpProbe on one leg of the heater contactor to verify) ...
❒
Yes
❒
No
Heating Mode Stop (Mechanical Heating Heat Pump)
Adjust the heating setpoint to approximately two degrees below the current indoor temperature. The
unit will sequence off, stop heating.
Did the Compressor stop? .................................................................................................
❒
Yes
❒
No
Did the Condenser Fan (CFM) stop? ................................................................................
❒
Yes
❒
No
Did the indoor blower motor (IBM) Stop? .......................................................................
❒
Yes
❒
No
** If you see readings that are out of the normal range or features that seem to be operating incor-
rectly. **
Please provide a description of the issue in the Notes section below and if you need help, call:
Marvair Technical and Warranty Support: (888) 726-2734
This number is manned M-F, 8:00am to 5:00pm eastern.
Technical support calls will be returned M-F, 5:00pm to 8:00pm eastern.
Only Emergency Dispatch calls will be returned M-F, 8:00pm to 8:00am Eastern (and week-
ends & holidays).