Marvair Classic AVHA Heat Pump I&O Manual

08/2018 Rev. 2

TO CLEAN FRESH AIR INTAKE FILTER:

A. Follow steps A and B at left 

“TO CHANGE SYSTEM FILTER”.

B. Gently pull out the filter from the 

bottom.

C. Wash the filter with water.

D. Reinstall the filter, by sliding it into the 

retaining rail.

E. Replace the access door and turn the 

power on to the unit.

2.  Keep the outdoor coil clean. Wash it down with a garden 

hose if necessary. 
BE SURE THE UNIT DISCONNECT IS IN THE “OFF” 

POSITION AND THAT ALL ELECTRICAL POWER TO 

THE UNIT IS TURNED OFF BEFORE CLEANING THE 

SYSTEM.

3.  Since the heat pump is located outdoors, it is exposed to 

all weather elements. Treat it with a good automobile paste 

wax twice a year (in the spring and fall).

Check with your contractor if you have any questions regarding 

the maintenance or operation of your unit.

 

INSTALLATION (A: CODES) 

The installer SHALL comply with all local, state, and federal 

codes and/or regulations pertaining to this type of equipment 

and its installation. Such codes and/or regulations should take 

precedence over any recommendations contained herein. 
Installations SHALL be made in accordance with the National 

Electrical Code, local codes, and recommendations made by 

the National Board of Fire Underwriters.

  INSTALLATION (B: UNIT SITE SELECTION) 

1.  To  eliminate  noise  from  being  transmitted  into  noise 

sensitive areas, the unit should NOT be installed on walls 

adjoining  bedrooms,  sleeping  quarters,  or  adjacent  to 

windows.

2.  Locating the unit as close as possible to the main duct 

system or area to be conditioned, will prevent lengthy duct 

runs and unnecessary thermal and air-pressure losses.

3.  The clearance to combustibles is 0” on all sides, and 1/4” 

for the first three (3) feet of supply duct.

4.  The  condenser  air  inlets  (left,  right  and  bottom  inlets) 

SHALL  be  located  at  least  8”  away  from  walls  or  other 

obstructions for unrestricted airflow.

5.  The  condenser  air  outlet  should  be  located  at  least  6’ 

away  from  any  obstructions  to  prevent  recirculation  of 

condenser air.

6.  Bottom of the unit SHALL be located at least 12” away from 

the ground or other obstructions for unrestricted airflow.

7.  Service  clearance  is  28”  from  the  electrical  box  access 

panel  located  on  the  front  of  the  unit  and  28”  from  the 

center, upper, and lower front access panels.

8.  The wall selected for unit installation MUST be able to or 

be made to safely support the weight of the unit.

9.  Do NOT locate where heat, lint or exhaust fumes will be 

discharged on the unit (as from dryer vents).

  INSTALLATION (C: UNIT PREPARATION) 

1.  AVHA  model  units  have  top  rain  flashing  built  onto 

the  unit.  The  bottom-mounting  flange  for  all  models  is 

shipped separately and in place. (Refer to “Section J. Unit 

Installation” for the recommended use of the bottom flange.)

2.  Electrical entrances are located on the right side and left 

side of all AVHA units. Refer to “Section H. Electrical Hook-

up” for details.

3.  Bend the lids of return and supply opening to form a return 

and supply air collars and install air gaskets.

4.  The supply and return air ducts should be checked to be 

sure they:

e.  Match the openings on the unit to be installed.

f.  Have the same distance between them vertically as 

the openings on the unit to be installed.

5.  Return and supply grilles must be used when the return 

and supply are not ducted. When a supply grille is used 

in the installation, the louver spacing must be no greater 

than 5/8 inch.

6.  If  the  factory-installed  filter  is  used  on  your  installation, 

access to the filter is made through the center panel on 

the front of the unit.

IF  A  REMOTE  FILTER  IS  USED,  SUCH  AS  A  FILTER 

GRILLE,  THE  FACTORY-INSTALLED  FILTER  MUST  BE 

REMOVED AND DISCARDED.

 

INSTALLATION (D: DUCTWORK) 

1.  Properly-sized  duct  systems  are  critical  for  satisfactory 

operation  of  any  air  conditioning  system.  All  ductwork 

MUST be correctly sized for the design air flow requirement 

of the equipment.

2.  The recommended operation duct static is to deduct 0.07” 

W.C. for any size of heater 5 kW to 20 kW on factory or 

field-installed heaters.

3.  Ductwork routed through wall cavities, as well as any duct 

not  in  conditioned  space,  MUST  be  insulated.  Supply 

ducting routed through exterior walls MUST be insulated 

with 1” insulation to the back of the unit.

4.  Supply and return air ducts should be flush with the exterior 

wall and sized to fit over the unit duct collars in order to 

compress the collar air gasket.

5.  If  supply  duct  is  flashed  to  the  exterior  of  a  building 

constructed with combustible material, the flashing MUST 

be insulated in order to maintain the required clearances 

to combustible materials. Required clearance is 1/4” for 

the first three (3) feet of supply duct.

 

INSTALLATION (E: FILTERS) 

1.  One-inch disposable filters are supplied standard in each 

unit.  Two-inch  disposable  filters  can  also  be  used  and 

are  available  as  an  option.  The  filter  rack  is  adjustable 

to accommodate 2” filters. The filter rack on this series is 

adapted by removing the 1” filter brackets. Refer to the 

Maintenance section for the procedures for changing the 

filters.

2.  If a filter grille is used in the installation, the filter should be 

properly sized to allow a maximum velocity of 400 FPM.

WHEN  A  FILTER  IS  USED,  THE  FACTORY-INSTALLED 

FILTER MUST BE REMOVED.

Содержание Classic AVHA36HPA

Страница 1: ...with INSTALLER Affix the instructions on the inside of the building adjacent to the thermostat END USER Retain this manual for future reference Heat Pump Product Manual Vertical Wall Mount Heat Pumps...

Страница 2: ...lure to follow these rules may result in death serious bodily harm property damage and damage to the equipment Important Safety Precautions 1 USE CARE when LIFTING or TRANSPORTING equipment 2 TRANSPOR...

Страница 3: ...ocal codes In the absence of local codes refer to the National Electrical Code NEC ANS NFPA No 70 1993 and recommendations made by the National Board of Fire Underwriters In all cases the equipment MU...

Страница 4: ...C UNIT PREPARATION 1 AVHA model units have top rain flashing built onto the unit The bottom mounting flange for all models is shipped separately and in place Refer to Section J Unit Installation for t...

Страница 5: ...ap The acceptable voltage range of the tap is as follows Tap Voltage Range 240 Volt 253 216 208 Volt 220 187 Six 6 conductor thermostat wires should be run from the thermostat location to the unit If...

Страница 6: ...ted on a coil tube When the thermostat closes the timer on the defrost control starts accumulating the compressor run time After the selected time 30 60 or 90 minutes has been accumulated the controll...

Страница 7: ...7 Marvair Classic AVHA Heat Pump I O Manual 08 2018 Rev 2 EXPLODED PARTS DRAWING 36 42 48 60...

Страница 8: ...WER WHEEL 100 9T CCW X X X X X X 14 421506 BLWR MTR BRKT X X X X X X X X X 14A 454280 BLWR MTR BRKT GROMMET TUBE X X X X X X X X X 14B 454282 BLWR MTR BRKT WASHER TUBE X X X X X X X X X 14C 454284 BLW...

Страница 9: ...9 CONTROL PANEL HV48 60 X X X X X X 31A T60 0093 TERMINAL BOARD PANEL HV48 60 X X X X X 32 T36 0036 CONTROL PANEL COVER HV36 X X X 32 T60 0036 CONTROL PANEL COVER HV48 60 X X X X X X 33 T36 0015 HEAT...

Страница 10: ...98 8 100 AVHA48HPA 208 230 1 60 33 0 50 59 0 60 85 0 90 105 8 110 AVHA60HPA 208 230 1 60 39 0 60 65 0 70 91 0 100 111 8 115 AVHA36HPC 208 230 3 60 16 0 30 34 0 40 43 0 50 61 0 70 AVHA42HPC 208 230 3 6...

Страница 11: ...Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Barometric Damper and No Heat Figure 3 Typical Wiring Diagram AVHA36 60 208 230V 1 w Bar...

Страница 12: ...A Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Motorized Damper and No Heat Figure 4 Typical Wiring Diagram AVHA36 60 208 230V 1 w Mot...

Страница 13: ...ic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 1 w Economizer and No Heat Figure 5 Typical Wiring Diagram AVHA36 60 208 230V 1 w Eco...

Страница 14: ...Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Barometric Damper and No Heat Figure 6 Typical Wiring Diagram AVHA36 60 208 230V 3 w Bar...

Страница 15: ...A Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Motorized Damper and No Heat Figure 7 Typical Wiring Diagram AVHA36 60 208 230V 3 w Mot...

Страница 16: ...ic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 208 230V 3 w Economizer and No Heat Figure 8 Typical Wiring Diagram AVHA36 60 208 230V 3 w Eco...

Страница 17: ...AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Barometric Damper and No Heat Figure 9 Typical Wiring Diagram AVHA36 60 460V 3 w Baromet...

Страница 18: ...AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Motorized Damper and No Heat Figure 10 Typical Wiring Diagram AVHA36 60 460V 3 w Motori...

Страница 19: ...lassic AVHA Heat Pump I O Manual 08 2018 Rev 2 Crispaire Division of AIRXCEL Inc Marvair Cordele GA AVHA36 60 460V 3 w Economizer and No Heat Figure 11 Typical Wiring Diagram AVHA36 60 460V 3 w Econom...

Страница 20: ...ELEMENT HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED Figure 12 Typical Wiring Diagram AVHA36 60 208 230V 1 5kW Heater Circuit Crispaire Division of AIRXCEL Inc Marvair Cordele GA FAN PURGE SECONDS...

Страница 21: ...HEATER ELEMENTS HEATER FAN PURGE SECONDS DOM MINUTES FAN SPEED GND SPPE Figure 14 Typical Wiring Diagram AVHA36 60 208 230V 1 15kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 6 KW H...

Страница 22: ...D DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 16 Typical Wiring Diagram AVHA36 60 208 230V 3 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE S...

Страница 23: ...PEED DOM MINUTES DL1 DL3 DL6 DL4 SWITCHES LIMIT 1 SHOT 2 1 Figure 18 Typical Wiring Diagram AVHA36 60 460V 3 6 9kW Heater Circuit Marvair Division of AIRXCEL Inc Cordele GA 3PH 15 KW HEATER FAN PURGE...

Страница 24: ...1 2 699 E 14 356 16 406 F 18 457 30 762 G 8 203 10 254 H 1 7 8 48 2 1 4 57 I 28 711 30 762 J 50 1 2 1 283 57 1 8 1 451 K 1 1 8 29 1 1 8 29 L 71 1 2 1 816 87 1 8 2 213 M 2 1 2 64 2 1 2 64 N 10 1 2 267...

Страница 25: ...o position damper open closed capable of 0 to 450 cfm of outside air includes pressure relief C Economizer capable of 100 of rated cooling capacity using outside air Electric Heat 000 No Heat 050 5 kW...