47
208V
MODEL
10K(L)
15K(L)
15K(L) DUAL
20K(L)
20K(L) DUAL
30KL
30KL DUAL
40KL
30KL DUAL
CAPACITY*
10KVA
/10KW
15KVA / 15KW
20KVA / 20KW
30KVA / 30KW 40KVA / 40KW
INPUT
Voltage
Range
Low Line Loss
70 VAC(Ph-N) ± 3 % at 50% Load
88 VAC(Ph-N) ± 3 % at 100% Load
Low Line Comeback
Low Line Loss V 5V
High Line Loss
156 VAC(L-N) ± 3 % at 50% Load
146 VAC(L-N) ± 3 % at 100% Load
High Line Comeback
High Line Loss Voltage - 5V
Frequency Range
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Phase
3 Phase with Neutral
Power Factor
≧
0.99 at 100% Load
OUTPUT
Phase
3 Phase with Neutral
Output voltage
208/220VAC (Ph-Ph)
120/127VAC (Ph-N)
AC Voltage Regulation
± 1%
Frequency Range
(Synchronized Range)
46Hz ~ 54 Hz @ 50Hz system
56Hz ~ 64 Hz @ 60Hz system
Frequency Range (Batt. Mode)
50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Overload
AC mode
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
Battery mode
100%~110%: 60min; 110%~125%: 10min; 125%~150%:1min;>150% : immediately
Current Crest Ratio
3:1 max
Harmonic Distortion
≦
2 % @ 100% Linear Load;
≦
4 % @ 100% Non-linear Load (PF≥0.8)
Transfer
Time
Line
Battery
0 ms
Inverter
Bypass
0 ms (When phase lock fails, <4ms interruption occurs from inverter to bypass)
Inverter
ECO
<10 ms
EFFICIENCY
AC mode
93.5%
Battery Mode
92.5%
BATTERY
Standard
Model
Type
12 V / 9 Ah
12 V / 9 Ah
12 V / 9 Ah
N/A
Numbers
(10+10)pcs x 1
string
(10+10)pcs x 2
strings
(10+10)pcs x 3
strings
Recharge Time
9 hours recover to 90% capacity
Charging Current(max.)
1A~12A± 10%
(Adjustable)
4A/8A/12A (Adjustable)
Optional parallel up to Max. 20A
Charging Voltage
+/-136.5 VDC ± 1%
Long-run
Model
Type
Depending on applications
Numbers
16 ~ 20 (adjustable)
Charging Current(max.) 1A~12A± 10%
(Adjustable)
4A/8A/12A (Adjustable)
Optional parallel up to Max. 20A
8A/16A/24A (Adjustable)
Charging Voltage
+/- 13.65 VDC * N ± 1% (N = 8~10)
PHYSICAL
Standard
Model
Dimension, D X W X H mm 667 x 250 x 827 865 x 300 x 1020
865 x 300 x 1020
N/A
Net Weight (kgs)
95
181
231
Long-run
Model
Dimension, D X W X H mm 667 x 250 x 827 865 x 300 x 1020
865 x 300 x 1020 790 x 420 x 1200 790 x 420 x 1200
Net Weight (kgs)
45
80
81
150
160
ENVIRONMENT
Operation Temperature
0 ~ 40°C (the battery life will down when > 25°C)
Operation Humidity
<95 % and non-condensing
Operation Altitude**
<1000m**
Acoustic Noise Level
Less than 58dB
@ 1 Meter
Less than 65dB
@ 1 Meter
Less than 70dB @
1 Meter
Less than 70dB
@ 1 Meter
Less than 75dB
@ 1 Meter
MANAGEMENT
Smart RS-232 or USB
Supports Windows® 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix, and MAC
Optional SNMP
Power management from SNMP manager and web browser
* If the UPS is installed or used in a place where the altitude is above than 1000m, the output power must be derated 1% per 100m.
**Product specifications are subject to change without further notice.