Maruson Ultima RT 10K Скачать руководство пользователя страница 33

 

30 

 

Warning 

10: IP Fuse Open 

Input  fuse  on  the  power  stage 

board is burnt. 

Check  and  replace  the  input 

fuse. 

Warning 

33: Overload 3Times  Locked in bypass after overload 3 

times in 30 minutes. 

Remove excess loads from UPS 

output first, then shut down the 

UPS and restart it. 

Warning 

3A: Maintain Open     EMBS port is open or the maintain 

switch sensor (connected to EMBS 

port)  is  trigged.  (The  UPS  is 

transferred to bypass). 

If 

the 

EMBS 

port 

is 

short-circuited, the warning will 

disappear. 

Warning 

3F: Para Protect     

Parallel cable is still not connected 

well when restart after the parallel 

system is fault because of parallel 

communication failure. (When this 

warning  appeared,  the  UPS  could 

not  start  up,  it  is  protection  for 

parallel system) 

1)

 

If the system is still needed 

to  be  operated  in  parallel 

mode,  please  connect  the 

parallel  cable  well,  and 

choose  “Para  Unlock”  in 

control menu to remove the 

warning,  then  the  UPS 

could start up. 

2)

 

If  the  UPSs  in  the  system 

are separated to single UPS, 

please 

disconnect 

the 

output  to  other  UPSs  and 

choose  “Para  Unlock”  in 

control menu to remove the 

warning,  then  the  UPS 

could start up. 

 

NOTE:  Be  careful  to  check 

the  UPS  operation  mode 

(parallel  or  single)  and  the 

connections.  If  the  parallel 

cable  is  not  connected  in 

the  parallel  mode,  the  UPS 

may be destroyed. 

Fault 

01: Bus Start Fail      The  internal  converter  failed,  so 

the  DC  bus  voltage  could  not  be 

boosted correctly. 

Contact the dealer for repair 

Fault 

02: Bus Over 

1)

 

The  mains  input  or  load 

transient current cause the DC 

bus voltage is too high; 

2)

 

The internal converter failed. 

1)

 

Shutdown  and  restart  the 

system to see if it happens 

again; 

2)

 

Contact  the  dealer  for 

repair. 

Fault 

03: Bus Under 

The  internal  converter  failed,  so 

the DC bus voltage is too low.   

Contact the dealer for repair. 

Fault 

04: Bus Unbalance 

1)

 

The  load  is  special  or 

abnormal,  so  the  internal 

positive  and  negative  DC  bus 

voltages are unbalanced; 

2)

 

The internal converter failed. 

Contact the dealer. 

Fault 

11: Inv Start Fail 

The internal inverter failed, so the 

inverter voltage could not start up       

correctly. 

Contact the dealer for repair. 

Fault 

12: Inv Volt High 

The internal inverter failed, so the 

inverter voltage is too high. 

Contact the dealer for repair. 

Fault 

13: Inv Volt Low 

The internal inverter failed, so the 

inverter voltage is too low. 

Contact the dealer for repair. 

Fault 

14: Output Short  

Short  circuit  occurs  on  the  UPS 

output. 

Remove the short circuit. 

Содержание Ultima RT 10K

Страница 1: ...l Info MarusonUSA com Copyright 2014 All Rights Reserved Maruson is a registered trademark of Maruson Technology U S Trademark Reg No 3 150 957 All other trademarks are the property of their respectiv...

Страница 2: ...instructions in this manual strictly Save this manual properly and read carefully the following instructions before installing the unit Do not operate this unit before reading through all safety info...

Страница 3: ...INE DIAGRAM 7 2 4 RACK TOWER TYPE INSTALLATION 8 2 5 SINGLE UPS INSTALLATION 9 2 6 OUTPUT CONFIGURATION 12 2 7 PARALLEL UPS INSTALLATION 14 3 OPERATIONS 15 3 1 OPERATING MODE STATUS DESCRIPTION 15 3 2...

Страница 4: ...ts Install your UPS in a structurally sound area Your UPS is extremely heavy take care when moving and lifting the unit Only operate your UPS at indoor temperatures between 32 F and 104 F between 0 C...

Страница 5: ...be done only by trained personnel During any service work to the UPS it should be turned off or manually bypassed Note that potentially lethal voltages exist within this unit as long as the battery su...

Страница 6: ...terminals with any object Unplug and turn off the UPS before performing battery replacement Battery replacement should be performed only by authorized service personnel using the same number and type...

Страница 7: ...cable and one share current cable option One battery cable option Tower type installation supporters Rack type installation ears Battery cable connection ears Sixteen M4 screws and four metal plates N...

Страница 8: ...5 Diagram 3 Battery Pack Rear Panel Diagram 4 ISO Bank Rear Panel Overlook Diagram 5 ISO Bank Output Terminal...

Страница 9: ...onnector 4 Share current port for parallel function 5 Parallel port for parallel function 6 Intelligent slot 7 EMBS External Maintain Bypass Switch port 8 Cooling fan 9 External battery connector 10 I...

Страница 10: ...mal operation To activate EPO function please remove the jumper WARNING The EPO circuit is an IEC 60950 safety extra low voltage SELV circuit This circuit must be separated from any hazardous voltage...

Страница 11: ...in 3U Assemble two feet and one short extension as one tower stand shown in step 1 Align the two stands approximately 35cm apart in step 2 Then put UPS module in the stands as shown in step 3 Step 1 S...

Страница 12: ...ant to help you lift the UPS module and slide it onto the mounting shelves attach the UPS module to the rack by passing the screws nuts and washers user provided through its mounting ears and into the...

Страница 13: ...ety and efficiency NOTE 2 The cable for Ultima RT 10K L should be able to withstand over 63A current It is recommended to use 8AWG or thicker wire for safety and efficiency NOTE 3 The selections for c...

Страница 14: ...d then install the battery pack Pay highly attention to the rated battery voltage marked on the rear panel If you want to change the numbers of the battery pack please make sure you modify the setting...

Страница 15: ...the final output of system The UPS s output connect to the input of ISO bank Option 1 The output of ISO bank There are 2 sets of low voltage outputs 104 110 115 120V on L1 N1 L2 N2 Each set is able t...

Страница 16: ...d to L1 N1 and L2 N2 and connect high voltage load to L1 N2 NOTE 1 If any load current in L1 N1 or L2 N2 is higher than 25A in 6K L model and 42A in 10K L model the UPS will still operate normally wit...

Страница 17: ...14 2 7 Parallel UPS Installation For parallel UPS installation please contact your dealer for more professional support...

Страница 18: ...or 60 Hz through the inverter The UPS will still charge battery at this mode There is no bypass at this mode Battery Mode When the input voltage is out of the acceptable range or power failure and th...

Страница 19: ...ery pack breaker is at ON position Set the external mains input breaker to ON position then the fan will be running and the UPS supplies power to the loads via bypass The UPS is operating in Bypass mo...

Страница 20: ...ed carefully to see if capacity of the UPS can cover due to the huge starting power consumption of this kind of load 3 If the UPS is overload the buzzer will beep twice every second 4 When the UPS is...

Страница 21: ...d also enter the control menu to select the instruction Turn Off to turn off the UPS Please refer to the section of LCD operation NOTE Here Turn Off means that UPS is not working on line converter ECO...

Страница 22: ...am below Main Interface Control Measurement Information Setting Alarm Page 1 Input Page 2 Output Page 3 Battery Page 4 Bypass Page 5 Charger Turn On Batt Test Mute Para Unlock Page 1 Bypass Page 2 ECO...

Страница 23: ...attery mode according to the setting and input status in reverse you could press the OFF ESC button to turn off the UPS to bypass mode or shutdown This has been mentioned on above section of Single UP...

Страница 24: ...mode or ECO mode or battery mode according to the setting and input status NOTE you could turn on UPS by pressing the ON ENTER button in home page no necessary enter into this control menu b On line...

Страница 25: ...icon 4 Para Unlock That means the instruction of parallel protection unlock It only appears when the LCD shows the warning 3F Para Protect that means the parallel system is in protection and could not...

Страница 26: ...ent value of the parameters such as voltage current frequency power capacity time etc Press UP or DOWN to explore the pages 3 7 2 4 Information Pages These pages display the information of parameters...

Страница 27: ...le Bypass disabled When selected automatic bypass is acceptable but manual bypass is not available Manual bypass means users manually operate UPS to Bypass mode for example in Line mode turning off th...

Страница 28: ...put voltage with 230Vac 240 Presenting the rated output voltage with 240Vac 2 Freq 50Hz The output frequency is setting for 50Hz 60Hz The output frequency is setting for 60Hz ATO If selected output fr...

Страница 29: ...Description 1 Batt Calibrate the battery voltage measurement the calibration range is from 0V to 5 7V the default value is 0V It is available on all operation modes 2 Inv Adjust the inverter output v...

Страница 30: ...tery Disable is default setting Backup Time Parameters Setting Batt Groups Set the number of battery group ranging from 1 to 6 The default value is 1 group Batt Cap Set the battery capacity such as 7A...

Страница 31: ...28 3 7 2 6 Alarm page This page record and display the faults or warnings event happened in history...

Страница 32: ...n device Warning 07 Over Charge 1 Battery numbers and its setting is not matching 2 Charger voltage is too high the charger failed 1 Correct the battery number or its setting 2 Disconnect the battery...

Страница 33: ...start up NOTE Be careful to check the UPS operation mode parallel or single and the connections If the parallel cable is not connected in the parallel mode the UPS may be destroyed Fault 01 Bus Start...

Страница 34: ...el cable well Fault 36 OP I Unbalance The output current is extremely unbalanced between the paralleled UPSs there is some error in the parallel system Contact the dealer for repair Fault 41 Over Temp...

Страница 35: ...Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperature Recharge Frequency Charging Duration 25 C 40 C...

Страница 36: ...ity 9 hours recover to 90 capacity Charging Current 1 A 10 max Charging Voltage 273 V based on battery numbers at 20 pcs Long Run Model Type Depending on applications Numbers 18 20 Charging Current 4...

Отзывы: