8
2-4. Rack/Tower type installation
2-4-1 Tower type installation
The UPS system is shipped with four plastic feet and 6 plastic extensions (2 short extension plus 6 long
extensions). Those can be used to tower mount the UPS’s power module (3U) or UPS’s power module and a
battery bank (6U) or UPS module with ISO bank and one battery bank (9U).
Install UPS module in 3U
Assemble two feet and one short extension
as one tower stand shown in step 1. Align
the two stands approximately 35cm apart in
step 2. Then, put UPS module in the stands
as shown in step 3.
Step 1 Step 2
Step 3
Install UPS module and one battery bank in
6U
Assemble two feet and two long extensions
as one tower stand shown in step 1. Align
the two stands approximately 35cm apart in
step 2. Then, put UPS module and battery
bank in the stands as shown in step 3. And
assemble these metal plates and M4 screws
as shown in step 4.
Step 1 Step 2
Step 3 Step 4