10
Cyclo 03 Directional user manual
6. Clip the bracket covers over the brackets with the long side of the
rectangular hole at 90% to the.Cyclo 03 Directional.
7. Hold the luminaire up to the mounting brackets. Slide the ends of the
mounting arms through the rectangular holes in the bracket covers and
into the mounting brackets.
8. Carefully supporting the luminaire, fully tighten the 3mm Allen screws in
the side of each mounting arm.
9. Check that the luminaire is totally secure.
AC power
It is the installer’s responsibility to ensure that all local safety regulations
and legal requirements are observed when installing and connecting the
Cyclo 03 Directional.
AC mains power compatibility and consumption data are given in the
Specifications section on page 31.
Warning!
Many installations use common neutral conductors in branch
circuit distribution boxes. The neutral lead in the cable must be
connected to the same RCD (ground fault circuit breaker) as the
live lead in the cable. If it is not, users are left unprotected from
the risk of potentially lethal electric shock. It is the installer’s
responsibility to ensure that the Cyclo 03 Directional’s neutral
conductor is connected to the same RCD as the live conductor.
Important! Cyclo 03 Directional luminaires incorporate four electronic
ballasts that “leak” a total current of between 0.8mA and 4mA to
ground (earth). Luminaires must be correctly connected to
ground so that this “leakage” current can be absorbed.
It is also important that installation is carried out correctly in
order to avoid unintentional tripping of the RCD (ground fault
circuit breaker). Because of the “leakage” current, we
recommend connecting a maximum of seven Cyclo 03
Directional luminaires per phase when circuits are protected by
a 30mA RCD. Bear in mind that some RCDs rated at 30mA may
trip when current leakage to ground is as low as 20mA.
Connecting to mains power
Cyclo 03 Directional luminaires have an ENSTO male connector built into
the casing for mains power input. A female ENSTO connector is supplied
with the luminaire for installation on the power supply cable.