FIGURE 2

VOLTAGE ADJUST

The screwdriver adjustable potentiometer adjusts the generator output voltage. Adjustment
clockwise increases the generator output voltage.

When using a remote voltage adjust rheostat, remove the jumper wire across terminals 6 and 7
and install a 2000 ohm 1/2 watt (minimum) rheostat. This will give ±10% voltage variation from
the nominal. (For ±5% voltage variation use a 1000 ohm 1/2 watt rheostat).   See Figure 2.

STABILITY ADJUST

System stability is the ability of the generator to respond to load transients. Decreasing the
stability makes the generator less sluggish and faster to respond to toad transients. If the stability
of the regulator is decreased too much, the generator will tend to hunt under steady state
conditions.

The screwdriver adjustable potentiometer adjusts the system stability. Adjustment clockwise
increases the stability. Increasing the stability increases the response time of the generator.
Conversely, decreasing the stability decreases the response time of the generator.

V/HZ ROLL-OFF FREQUENCY SELECTION

The roll off point is the frequency where the generator voltage starts to decrease. This reduces
the Kilowatt load to the engine, which allows the engine to recover in speed under any load
transient condition. Use jumper to select 50 HZ or 60 Hz. The screwdriver adjustable
potentiometer sets the roll-off frequency from 54-61 Hz in the 60 Hz setting or from 45-51 Hz in
the 50 Hz setting.

The SE350 has the roll-off point preset to 58 Hz in the 60 Hz mode and 48 Hz in the 50 Hz
mode. To change the roll-off point, adjust engine speed to the desired rated speed. (50 or 60 Hz).
Set the voltage to the desired setting at rated speed. Adjust engine speed to the desired roll-off
point. Turn the potentiometer counterclockwise until the voltage starts to drop off. Then adjust
the potentiometer clockwise until the voltage returns to rated voltage. Re-adjust engine speed to
rated speed.

Содержание AVR SE350

Страница 1: ...age 1 Instruction Manual I nst alla tio n Operation Maintenance Voltage Regulator hanada technology Co Ltd Tel 86 577 86065765 Fax 86 577 56854565 Email sale hnd avr com www hnd avr com Marthon AVR SE350 ...

Страница 2: ...SE350 VOLTAGE REGULATOR INSTRUCTION MANUAL ...

Страница 3: ...ostat Frequency Compensation Adjustable Roll off frequency 54 61 Hz for 60 Hz 45 51 Hz for 50 Hz Operation Weight6 5 oz Operating Temperature 40 C to 60 C Storage Temperature 65 C to 85 C Power Dissipation 8 watts maximum Size 3 94 L X 2 66 W X 2 20 H Voltage Buildup Internal provisions forautomatic voltage build up from generator residual voltage as low as 10 Vac EMI Suppression Internal Electrom...

Страница 4: ... rear face of the voltage regulator EXCITER POWER CIRCUIT Connect the regulator wire F to the generator F or Fl field terminal Connect the regulator wire F to the generator F or F2 field terminal See Figure 2 for typical connection diagram SENSING POWER INPUT CIRCUIT Input power and sensing is achieved through terminals 3 and 4 The voltage input requirement of the SE350 is 190 to 240 Vac See Figur...

Страница 5: ... Increasing the stability increases the response time of the generator Conversely decreasing the stability decreases the response time of the generator V HZ ROLL OFF FREQUENCY SELECTION The roll off point is the frequency where the generator voltage starts to decrease This reduces the Kilowatt load to the engine which allows the engine to recover in speed under any load transient condition Use jum...

Страница 6: ...t upon connection If it does not build up refer to field flashing section in generator manual Slowly adjust the voltage control until the generator voltage reaches the nominal value If used adjust the remote voltage rheostat to set the generator voltage to the exact value desired Turn the stability adjust counter clockwise until instability is shown on either of the voltmeters mentioned in the PRE...

Страница 7: ...s adjust turned down Remote voltage adjust is turned down Defective regulator Check wiring diagram for proper connections Rotate voltages adjust CW until desired voltage is reached Rotate remote voltages adjust CW until desired voltage is reached Replace regulator Output Voltage High Voltages adjust turned too high Remote voltage adjust is turned too high Rotate voltages adjust CCW until desired v...