5/25
55208033-08
PERFORMANCE DATA (kW)
NOTE THAT THERE ARE 3 SPEED RANGES OF LOW, MEDIUM AND HIGH
Range 3 = highest for maxium duties
Range 2 = medium for normal operations
Range 1 = lowest for minimum noise levels
UK CONDITIONS
ROOM 21°C/15°C
AMBIENT 27°C/19°C
EUROVENT
(NEMA)
ROOM
27°C/19°C
AMB 35°C/24°C
TROPICAL
ROOM
29°C/19°C
AMB 46°C/24°C
RANGE 3
LOW
MEDIUM
HIGH
HIGH
HIGH
RANGE 2
LOW
MEDIUM
HIGH
RANGE 1
LOW
MEDIUM
HIGH
600
(ALL)
MCU+
or
DCU+
TOT
SHR
SENS TOT
SHR
SENS
TOT
SHR SENS TOT
SHR SENS TOT
SHR SENS TOT
SHR
SENS
TOT
SHR SENS
20
15
1.77
0.75
1.33
1.82
0.80
1.46
1.87 0.85 1.59 1.91 0.92 1.75 1.94 1.00 1.94 2.13
1.00
2.13
2.05 1.00 2.05
20
20
2.28
0.69
1.58
2.35
0.72
1.70
2.40 0.76 1.83 2.45 0.81 1.99 2.50 0.88 2.19 2.65
0.93
2.47
2.28 1.00 2.28
20
30
N/A*
2.63
0.70
1.84
2.71 0.73 1.97 2.78 0.77 2.14 2.85 0.83 2.35 3.03
0.86
2.61
2.37 1.00 2.37
40
30
3.13
0.67
2.09
3.29
0.68
2.25
3.40 0.71 2.41 3.52 0.74 2.61 3.60 0.79 2.84 3.86
0.81
3.14
3.06 1.00 3.06
40
40
3.50
0.66
2.30
3.69
0.67
2.47
3.84 0.69 2.63 3.98 0.71 2.83 4.09 0.75 3.06 4.27
0.77
3.30
3.84 0.93 3.57
40
50
N/A*
4.59
0.66
3.01
4.83 0.67 3.22 5.05 0.69 3.47 5.27 0.72 3.78 5.66
0.72
4.08
4.73 0.89 4.20
60
40
3.60
0.66
2.39
3.79
0.68
2.58
3.92 0.70 2.76 4.06 0.73 2.98 4.18 0.78 3.25 4.33
0.81
3.52
3.87 0.99 3.84
60
50
4.35
0.65
2.82
4.66
0.66
3.06
4.89 0.67 3.26 5.14 0.68 3.51 5.35 0.71 3.81 5.72
0.72
4.09
4.80 0.88 4.20
60
60
N/A*
4.97
0.65
3.24
5.24 0.66 3.45 5.51 0.67 3.71 5.78 0.70 4.02 6.26
0.69
4.32
5.18 0.84 4.36
* Cannot be used on low speed
Rated at BS2852: Part 1: 1982: UK condition C; NEMA condition A; Tropical condition B
HEAT PUMP
a. Cooling (MAX speed outdoor unit fan)
UK CONDITIONS
ROOM 21°C/15°C
AMBIENT 27°C/19°C
EUROVENT (NEMA)
ROOM 27°C/19°C
AMBIENT 35°C/24°C
RANGE 3
LOW
MEDIUM
HIGH
HIGH
RANGE 2
LOW
MEDIUM
HIGH
RANGE 1
LOW
MEDIUM
HIGH
600
(ALL)
MHPUL
MHPUE
DHPUE
TOT SHR
SENS
TOT
SHR SENS TOT SHR SENS TOT SHR SENS TOTAL SHR SENS
TOTAL
SHR
SENS
20
15
1.77 0.75
1.33
1.82
0.80 1.46 1.87 0.85 1.59 1.91 0.92 1.75 1.94 1.00 1.94
2.23
1.00
2.23
40
30
3.13 0.67
2.09
3.29
0.68 2.25 3.40 0.71 2.41 3.52 0.74 2.61 3.60 0.79 2.84
3.86
0.81
3.14
60
50
4.35 0.65
2.82
4.66
0.66 3.06 4.89 0.67 3.26 5.14 0.68 3.51 5.35 0.71 3.81
5.72
0.72
4.09
b. Heating (Room 20°C/12°C, outdoor unit fan at MAX speed)
HEATING OUTPUT AT 7°C AMBIENT
(EUROVENT)
HEATING OUTPUT AT -1°C AMBIENT
RANGE 3
LOW
MEDIUM
HIGH
LOW
MEDIUM
HIGH
RANGE 2
MEDIUM
HIGH
MEDIUM
HIGH
RANGE 1
HIGH
HIGH
600
(ALL)
MHPUL
MHPUE
DHPUE
kW
COP
kW
COP
kW
COP
kW
COP
kW
COP
kW
COP
20
15
2.06 2.50 2.07 2.52 2.13 2.60 1.58 2.10 1.68 2.20 1.72 2.23
40
30
2.92 2.70 2.98 2.75 3.46 3.23 2.30 2.30 2.40 2.40 2.60 2.60
60
50
5.48 2.48 5.68 2.58 5.71 2.89 4.42 2.31 4.64 2.31 4.75 2.59
Heronhill - for all your Marstair requirements
Tel: 01823 665660
www.heronhill.co.uk
Fax: 018123 665807