Auxiliary Electric Heat 

Installation, Operation & Maintenance Instructions

HG Series Electric Heaters

Overview

The HG Series Auxiliary Electric Heat mounts externally 

to the blower outlet of all HE. For the H

Z

 Series it mounts 

externally on the horizontals and internally on the 

vertical 

upflow and downflow units. It mounts internally 

on all 

WDG units.Note model compatibility Table 1. Units are 

rated for zero clearance at the unit and 1” clearance for 

first three feet of duct. The discharge plenum should make 

a 90° turn after leaving the unit and be constructed from 

non combustible material. The HG electric heat contains a 

four stage relay control board which activates the elements 

directly via an internally wired low voltage harness. Low 

voltage signals (W1 and W2) are staged from the 

D

XM 

(AXM on WDG Series) control of the unit.

Figure 1:  Typical Vertical External Mount Installation

Electric Heat Assembly

HG Installation - External Mount

1. Disconnect power to the unit.

2. Remove blower access panel(s) from the unit and 

control box and element covers from the electric heater.

3.

Locate remove and discard blower discharge flanges

from the unit but save the screws. Flanges will be

packaged loose inside the blower compartment of

vertical upflow units and will be factory installed on

horizontal units, downflow units have none. HE036

and 042 units require a transition bracket between

the cabinet panel and the electric heater. This bracket

is packaged inside the blower compartment for field

installation.

4. Position the electric heater as illustrated herein.

Heater control box should be facing the front access

panel of vertical units. For horizontal units notice that

the discharge air opening is off centered in the blower

panel. The electric heater must be positioned so that

its control box is located vertically over the wide side

of this panel.

The electric heater air inlet dimensions should match

the unit air outlet, installer should stop and refer

to the unit/heater compatibility chart later in this

instruction or consult factory if they do not match.

5.

Use the saved blower flange screws to attach the

heater by its flanges to the unit panel except do not

fasten flange on control box side.

6. Use aluminum tape (not provided) to seal all four

heater flanges to the blower panel.

7.

Locate and route the low voltage control harness

through one of the unit corner post or blower panel

knockout(s). Seal the penetration ‘air tight’.

8.

Route the control harness through one of the ‘pie’ 

bushings in the heater control box and plug on to the

P2 connector. See figure 3.

9. Install power conduit and attach directly to the

electric heater control box. See figures 5a-c.

10. Replace all covers and panels, heater installation is

complete. Proceed to wiring and setup.

Figure 1a: Typical Vertical Internal Mount

Содержание Comfort-Aire Century HG Series

Страница 1: ...the screws Flanges will be packaged loose inside the blower compartment of vertical upflow units and will be factory installed on horizontal units downflow units have none HE036 and 042 units require...

Страница 2: ...on or consult factory if they do not match 5 Re install blower assembly on to electric heater using pins and bolts as before Check blower electrical wiring for proper connection and remedy any pinched...

Страница 3: ...ectric heat model from Table 1 Low speed blower not allowed with electric heat Field supplied disconnect Refer to local codes Electric Heat Assembly Disconnect optional refer to local code Field suppl...

Страница 4: ...h setting Momentarily short the test pins do not jumper the test pins of the DXM control to place it in test mode to reduce time delays Unit will require 15 20 seconds before engaging emergency heat m...

Страница 5: ...500 HGM8A X 7 6 5 7 25900 19400 650 HGM10A X 9 6 7 2 32700 24600 650 HGM12A 11 4 8 6 38900 29200 750 HGM4B 3 8 2 9 13000 9900 500 HGM5B 4 8 3 6 16300 12300 500 HGM8B 7 6 5 7 25900 19400 650 HGM10B 9 6...

Страница 6: ...40 34 7 7 0 59 52 60 60 HGL15 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 20 17 3 7 0 34 30 35 30 HGL20 DUAL L1 L2 40 34 7 0 0 50 43 50 45 L3 L4 40 34 7 7 0 59 52 60 60 All heaters rated single phase 208...

Страница 7: ...n HGL Large Electric Heat Option 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3 13 3 13 5 2 15 1 12 Discharge Air Opening Discharge Air Opening 14 7 Control box Element cover 10 3 15 5 16 8 8 1 3...

Страница 8: ...WDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW DSSOLFDEOH UHJXODWLRQV LQ HIIHFW RQ GDWH RI PDQXIDFWXUH KRZHY...

Отзывы: