Service Manual -
HRG18xxS1P
508206-01
Issue 2140
Page 20 of 83
Thermostat Type
Indoor Unit Type
Qty. of
Wires to
HRG18
HRG18 Terminal
Strip Connections
Unit Operation
Field Wiring
Diagram
Conventional
24VAC 2-Stage
Cooling
Thermostat (non-
communicating)
Any Furnace or
Air Handler (non-
communicating)
6
R, C, W1, O, Y1, Y2
Full Variable Capacity Operation
Controlled by HRG18 Unitary Control
Using Suction Pressure
Figure 13
Conventional
24VAC Single-
Stage Cooling
Thermostat (non-
communicating)
Any Furnace or
Air Handler (non-
communicating)
5
R, C, W1, O, Y1
(Jumper Y1 to Y2)
Full Variable Capacity Operation
Controlled by HRG18 Unitary Control
Using Suction Pressure
Figure 12
Table 6. HRG18 Thermostat Control Options
Install Thermostat
Install room thermostat (ordered separately) on an inside
wall approximately in the center of the conditioned area
and 5 feet (1.5m) from the floor. It should not be installed
on an outside wall or where it can be affected by sunlight
or drafts.
THERMOSTAT
5 FEET
(1.5M)
Figure 10.
NOTE:
24VAC, Class II circuit connections are made in
the control panel.
Size Circuit and Install Service Disconnect
Switch
Refer to the unit nameplate for minimum circuit ampacity,
and maximum fuse or circuit breaker (HACR per NEC).
Install power wiring and properly sized disconnect switch.
SERVICE
DISCONNECT
SWITCH
MAIN FUSE
BOX/BREAKER
PANEL
Figure 9.
NOTE:
Units are approved for use only with copper
conductors. Ground unit at disconnect switch or connect
to an earth ground.