background image

5

1)

Restore the system power.  The LCD (liquid crystal display) will
alternately display the time and room temperature.  The LCD will
illuminate at the touch of the red or blue arrow keys.  LCD will
return to its normal state after 10 seconds. 

2)

Set the fan switch to the 

ON

position.  The system blower should start.

3)

Set the fan switch to the 

AUTO

position.  The system blower should stop.   

4)

Set the system switch to the 

HEAT

position and depress the red

arrow key until the temperature set point is at least 3 degrees
above the room temperature.  The LCD will display a flame icon to
indicate heat.  The heating system should start within several sec-
onds (the system blower may not come on immediately).

5)

Set the system switch to the 

OFF

position.  The system should shut down within several seconds.  The LCD

will again alternately display the time and room temperature.  

6)

Set the system switch to the 

COOL

position and depress the blue arrow key until the temperature set point is

at least 3 degrees below the room temperature.  The LCD will dis-
play a snowflake icon to indicate A/C.  The cooling system should
start within several seconds.  

WARNING:

Do not perform this test

if the outdoor temperature is below 50 F.

7)

Set the system switch to the 

OFF

position. The system should shut

down within several seconds.  The LCD will again alternately display the time and room temperature.  

Programming The User Settings

Temperature Differential

is factory set at .5 F (0.25 C) for both heating and cooling cycles.  The room tempera-

ture must change .5 F (0.25 C) from the set point temperature before the thermostat will initiate a call for heat or
A/C.  This should be appropriate for most applications.  However, if the system is cycling on and off too frequent-
ly, the setting can be adjusted as follows.

Image shows display alternating between time
and a room temperature of 70

Image shows room temperature of 71 and Heat set
point of 75 as the display alternates every 3 seconds.

Image shows room temperature of 76 and A/C set
point of 73 as the display alternates every 3 seconds.

70814-IM  12/22/06  2:00 PM  Page 5

Содержание 70814

Страница 1: ...INSTALLATION AND OPERATING INSTRUCTIONS 7 Day Programmable Electronic Thermostat 2 Heat 2 Cool Non Heat Pump Model 70814 70814 IM 12 22 06 2 00 PM Page 1...

Страница 2: ...ostat is equipped with automatic compressor protection to prevent damage due to short cycling The short cycle protection provides a 5 minute delay between cooling cycles to prevent the compressor from...

Страница 3: ...e best viewed from a front downward angle 3 Remove the back plate of the thermostat by gently depressing the bottom locking tab and swinging the back plate up and away 4 Place the back plate against t...

Страница 4: ...for the front body to properly snap into place 11 Set the system switch to the OFF position 12 Set the fan switch to the AUTO position 13 Open the front thermostat door and open the battery compartme...

Страница 5: ...he temperature set point is at least 3 degrees below the room temperature The LCD will dis play a snowflake icon to indicate A C The cooling system should start within several seconds WARNING Do not p...

Страница 6: ...RAM and RUN keys three times The LCD will display the fan delay setting in seconds Use the red and blue arrow keys to set the delay time to the desired setting of 0 30 or 60 seconds 2 When the desired...

Страница 7: ...62 F 62 F 62 F 62 F 62 F 62 F 16 5 C 16 5 C 16 5 C 16 5 C 16 5 C 16 5 C 16 5 C 8 00am 8 00am 8 00am 8 00am 8 00am 8 00am 8 00am Cool 85 F 85 F 85 F 85 F 85 F 85 F 85 F 29 5 C 29 5 C 29 5 C 29 5 C 29 5...

Страница 8: ...Depress the PROGRAM key to select the desired period Each depression of this key cycles the menu to the next period Depress the Time Day key to switch between time settings and temperature settings a...

Страница 9: ...from temperature setback periods Efficient Recovery Mode activates when heating or cooling is called upon by the program to bring the room temperature to a desired level Instead of using both heating...

Страница 10: ...gs including the program All user entered settings will be lost The reset will also override the 5 minute compressor protection feature To reset the thermostat gently press the reset button on the fro...

Страница 11: ...rate and a low differential increases cycle rate not enough Display is not illuminated Touch the up or down arrow key Display will illuminate for 10 seconds Room temperature and Normal depending on d...

Страница 12: ...ing Diagrams R C G Y1 Y2 W1 W2 B O 24 VAC TRANSFORMER COM HOT 2nd STAGE COMPRESSOR Typical Multi Stage System FAN CONTROL 1st STAGE COMPRESSOR 1st STAGE HEAT 2nd STAGE HEAT 70814 IM 12 22 06 2 00 PM P...

Страница 13: ...13 70814 IM 12 22 06 2 00 PM Page 13...

Страница 14: ...14 70814 IM 12 22 06 2 00 PM Page 14...

Страница 15: ...who purchased the product from a wholesaler For warranty claims consumers should contact the contractor or dealer who installed the thermostat This warranty and Motors Armatures liability does not inc...

Страница 16: ...INSTALLATION AND OPERATING INSTRUCTIONS 7 Day Programmable Electronic Thermostat 2 Heat 2 Cool Non Heat Pump Model 70814 70814 IM 12 22 06 2 00 PM Page 16...

Отзывы: