INSTALLATION OF RECESS MOUNTED

HEATER IN PLASTER CEILING

1. Determine the desired location of the heater.   SEE

WARNING NO. 4 FOR MIN. MOUNTING
CLEARANCES AND WARNING NO. 9.

2. Cut a 22-1/4” x 22-1/4” (565mm x 565mm) mounting

hole in the ceiling for the recess mounting box (Figure
5).

3. Remove the Recess Mounting Box (Figure 6) from the

carton containing the Recess Mounting Enclosure, Type
REA.

4. Remove one of the knockouts and install a cable or con-

duit connector (Figure 6).

5. Install the optional disconnect switch (if required) as

shown in Figure 6.

6. Run the power supply cable through the connector, leav-

ing about 8” (203mm) of wire inside the recess mounting
box.  (Power supply cable must be #10 AWG min. rated
90°C min.)

7. Place the recess mounting box in the ceiling opening

and align the marks on the sides of the mounting box
with the bottom of the finished ceiling (Figure 7).  This
will position the edge of the mounting box 3/8” (9,5mm)
below  the ceiling and will allow the recess face plate
to lay flat against the ceiling.

8. Secure the recess mounting box to the building structure

using a minimum of four fasteners (not supplied).

9. Remove the heater section from its carton.

10. Install optional controls (if required) into the heater sec-

tion in accordance with the Instruction Sheet packaged
with the control.

11. To wire the heater, and/or to convert from single to

three-phase voltage, refer to “Electrical Wiring” (Figure
12, page 5).

12. Position the heater section over the studs in the recess

mounting box (Figure 8).

NOTE: The end of the heater section with the terminal
block must be positioned at the end of the recess mounting
box where the supply wiring enters.

13. Push the heater section onto the studs and securely

tighten four nuts (supplied) on the studs to secure the
heater section to the recess mounting box (Figure 8).

14. Connect the ground wire to the green ground screw on

the recess mounting box.

15. Remove the recess face plate (Figure 8) from the carton

containing the Recess Mounting Enclosure, Type REA.

16. Position the recess face plate over the heater

section/recess mounting box, making sure that the
thumb pins are in the holes in the heater section. 

NOTE: The thumb pins are an aid to help position and hold 
the recess face plate during installation.  Additional support 
(Step 18) is required.  SEE WARNING PAGE 2.

4

Figure 4

Figure 5

Figure 6

Figure 7

Figure 8

Power Supply

Cable

T-

Bar

Grid

Heater

Wall

Wall

12”(305mm) Min.4kw
24”(609mm) Min. 5kw

12”(305mm) Min.4kw
24”(609mm) Min. 5kw

Wall

Wall

Wall

Wall

22-1/4”
(565mm)

22-1/4”
(565mm)

12”(305mm) Min.4kw
24”(609mm) Min. 5kw

8”(2438mm) to Floor Min.
14”(4267mm) to Floor Max..

12”(305mm) Min.4kw
24”(609mm) Min. 5kw

Optical 
Disconnect 
Switch

Recess
Mounting
Box

Recess Mounting
Box

Recess Face
Plate

Heater
Section

Insure that “Thumb Pin” is pulled
out before positioning the face
plate on the heater section.
Depress “Thumb Pin” after face
plate is sealed firmly against the
heater section.

Thumb Pin Hole

Nut (4)

Stud (4)

Screw (4)

Power
Supply
Cable

3/8” (9.5mm)

Recess
Mounting Box

Cable or
Conduit
Connector

1/2” (12.2mm)
Knockout

Screw (2)

1/2” (12.2mm)
Knockout

7/8” & 1-1/8”
(22.2 & 28.5mm)
Nested Knockout

7/8” & 1-1/8”
(22.2 & 28.5mm)
Nested Knockout

Grounding
Screw

Содержание 542

Страница 1: ...n any manner Keep combustible materials such as crates drapes etc away from heater 7 A heater has hot and arcing sparking parts inside Do not use it in areas where gasoline paint or flammable liquids are stored 8 This heater is not approved for use in corrosive atmos pheres such as marine green house or chemical storage areas 9 The heater enclosure must be securely mounted to ceil ing or framing c...

Страница 2: ...th the control IMPORTANT Field Conversion for Lower Wattage Rating Figure 12 To convert the heater to a lower wattage rating completely remove one 1 red jumper wire from one heating element for 25 wattage reduction Completely remove two 2 red jumper wires for a 50 wattage reduction Discard the jumper s Be sure the remaining wires are securely connected Conversion for 3Ø Installation Heater is fact...

Страница 3: ...le to three phase voltage refer to Electrical Wiring Figure 12 page 5 8 Position the heater section over the studs in the recess mounting box Figure 3 NOTE The end of the heater section with the terminal block must be positioned at the end of the recess mounting box where the supply wiring enters 9 Push the heater section on to the studs and securely tighten four nuts supplied on the studs to secu...

Страница 4: ...mounting box Figure 8 NOTE The end of the heater section with the terminal block must be positioned at the end of the recess mounting box where the supply wiring enters 13 Push the heater section onto the studs and securely tighten four nuts supplied on the studs to secure the heater section to the recess mounting box Figure 8 14 Connect the ground wire to the green ground screw on the recess moun...

Страница 5: ...g air to flow from the center of the heater 2 After the operational check set the thermostat to obtain the desired comfort level NOTE Heater contains a fan delay on shut down The fan energizes immediately when the thermostat turns on the elements Fan will operate for a short time after the heating ele ments are turned off approx 1min TO WIRE 3Ø REFER TO STANDARD WIRING DIAGRAM COMPLETELY REMOVE BL...

Страница 6: ...g both available from Marley Engineered Products When requesting return authorization include all catalog numbers shown on the products HOW TO ORDER REPAIR PARTS In order to obtain any needed repair or replacement parts warranty service or technical information please contact Marley Engineered Products Service Center toll free by calling 1 800 642 HEAT When ordering repair parts always give the in...

Отзывы: