Marley 542 Скачать руководство пользователя страница 3

9. To wire the heater, and/or to convert from single to

three-phase voltage, refer to “Electrical Wiring” (Figure
12, page 5).

10. Position the heater section over the studs on the surface

mounting plate (Figure 2).

NOTE: The end of the heater section with the terminal
block must be positioned at the end of the surface mounting
plate where the supply wiring enters.

11. Push the heater section onto the studs and securely

tighten four nuts (supplied) on the studs to secure the
heater section to the surface mounting plate (Figure 2).

12. Remove the Surface Wrapper from the carton containing

the Surface Mounting Enclosure, Type SEA.

NOTE: Insure that the “thumb pin” in each end of the dis-
charge grille opening is pulled outward to allow the body of 
the thumb pins to fit into the holes in the heater section. 
(Figure 2).

13. Position the surface wrapper over heater section/surface

mounting plate, making sure that the thumb pins are in
the holes in the heater section.

14. With the surface wrapper seated firmly against the

heater section, depress the “thumb pins”.  This will
cause the thumb pins to expand and will temporarily
hold the surface wrapper in place.

NOTE: The thumb pins are an aid to help position and hold 
the surface wrapper during installation.  Additional support 
(step 15) is required.  SEE WARNING PAGE 2.

15. Install and securely tighten four screws (supplied) to

secure the surface wrapper to the heater section (Figure
2).

16. Install discharge air grilles.  (Refer to “Installation of

Discharge Air Grilles”, page 5.)

INSTALLATION OF RECESS MOUNTED 

HEATER IN T-BAR CEILING

The recess mounted heater will mount in any standard 2’ x 
2’ (609mm x  609mm) T-Bar (drop) ceiling.  SEE WARNING 
NO. 4 FOR MIN. MOUNTING CLEARANCES & WARNING 
NO. 9.

1. Remove the recess mounting box (Figure 3) from the

carton containing the Recess Mounting Enclosure, Type
REA.

2. Remove three screws and the side of the recess mount-

ing box to allow for easier wiring (Figure 3).

3. Remove one of the knockouts and install a cable or con-

duit connector (Figure 3).

4. Install the optional disconnect switch (if required as

shown in Figure 3).

5. Remove the heater section from its carton.
6. Install optional controls (if required) into the heater sec-

tion in accordance with the Instruction Sheet packaged
with the control.

7. To wire the heater, and/or to convert from single to

three-phase voltage, refer to “Electrical Wiring” (Figure

12, page 5).

8. Position the heater section over the studs in the recess

mounting box (Figure 3).

NOTE: The end of the heater section with the terminal 
block must be positioned at the end of the recess mounting 
box where the supply wiring enters.

9. Push the heater section on to the studs and securely

tighten four nuts (supplied) on the studs to secure the
heater section to the recess mounting box (Figure 3).
See Warning page 2.

10. Remove the Recess Face Plate (Figure 3) from the car-

ton containing the Recess Mounting Enclosure, Type
REA.

NOTE: Insure that the “thumb pin” in each end of the dis-
charge grille opening is pulled outward to allow the body of 
the thumb pins to fit into the holes in the heater section.  
(Figure 3.) See warning page 2.

11. Position the recess face plate over the heater

section/recess mounting box, making sure that the
thumb pins are in the holes in the heater section.

12. With the recess face plate seated firmly against the

heater section, depress the “thumb pins”.  This will
cause the thumb pins to expand and will temporarily
hold the recess face plate in place.

NOTE: The thumb pins are an aid to help position and hold 
the recess face plate during installation.  Additional support 
(Step 13) is required.  SEE WARNING PAGE 2.

13. Install and securely tighten four screws (supplied) to

secure the recess face plate to the heater section
(Figure 3).

14. Determine the desired location of the heater.
15. Position the heater in the T-bar grid (Figure 4) and

secure as required.  SEE WARNING NO. 9.

16. Run the power supply cable through the connector, leav-

ing about 8” (203mm) of wire inside the recess mounting
box.  (Power supply cable must be #10 AWG min. rated
90°Cmin.)

17. Connect the ground wire to the green ground screw on

the recess mounting box.

18. After wiring is complete, replace and secure the side of

the recess mounting box previously removed in Step 2.

19. Install discharge air grilles.  (Refer to “Installation of

Discharge Air Grilles”, page 5.)

3

Figure 3

Thumb Pin

Hole (2)

Thumb 

Pin (2)

Insure that “Thumb Pin” is pulled out
before positioning the face plate on
the heater section.  Depress “Thumb
Pin” after face plate is sealed firmly
against the heater section.

Screw (4)

Screw (3)

Screw (2)

Recess Face

Plate

Recess

Mounting Box

Heater Section

Nut (4)

Stud(4)

Cable or 

conduit

connector

Optional
Disconnect 
Switch

1/2” (12.7mm) Knockout 

7/8” & 1-1/8” (22.2mm & 28.5mm) Knockout

7/8” & 1-1/8” 
(22.2mm & 28.5mm) 
Nested Knockout

1/2”(12.7mm) Knockout 

Side 
Panel

Grounding Screw

Содержание 542

Страница 1: ...n any manner Keep combustible materials such as crates drapes etc away from heater 7 A heater has hot and arcing sparking parts inside Do not use it in areas where gasoline paint or flammable liquids are stored 8 This heater is not approved for use in corrosive atmos pheres such as marine green house or chemical storage areas 9 The heater enclosure must be securely mounted to ceil ing or framing c...

Страница 2: ...th the control IMPORTANT Field Conversion for Lower Wattage Rating Figure 12 To convert the heater to a lower wattage rating completely remove one 1 red jumper wire from one heating element for 25 wattage reduction Completely remove two 2 red jumper wires for a 50 wattage reduction Discard the jumper s Be sure the remaining wires are securely connected Conversion for 3Ø Installation Heater is fact...

Страница 3: ...le to three phase voltage refer to Electrical Wiring Figure 12 page 5 8 Position the heater section over the studs in the recess mounting box Figure 3 NOTE The end of the heater section with the terminal block must be positioned at the end of the recess mounting box where the supply wiring enters 9 Push the heater section on to the studs and securely tighten four nuts supplied on the studs to secu...

Страница 4: ...mounting box Figure 8 NOTE The end of the heater section with the terminal block must be positioned at the end of the recess mounting box where the supply wiring enters 13 Push the heater section onto the studs and securely tighten four nuts supplied on the studs to secure the heater section to the recess mounting box Figure 8 14 Connect the ground wire to the green ground screw on the recess moun...

Страница 5: ...g air to flow from the center of the heater 2 After the operational check set the thermostat to obtain the desired comfort level NOTE Heater contains a fan delay on shut down The fan energizes immediately when the thermostat turns on the elements Fan will operate for a short time after the heating ele ments are turned off approx 1min TO WIRE 3Ø REFER TO STANDARD WIRING DIAGRAM COMPLETELY REMOVE BL...

Страница 6: ...g both available from Marley Engineered Products When requesting return authorization include all catalog numbers shown on the products HOW TO ORDER REPAIR PARTS In order to obtain any needed repair or replacement parts warranty service or technical information please contact Marley Engineered Products Service Center toll free by calling 1 800 642 HEAT When ordering repair parts always give the in...