4. MARK Secure 2 installation instructions
Reinforced concrete ceiling, suspended ceiling
system, socket installation
Anchor device type A according to EN 795:2012 for
installation on reinforced concrete ceilings or reinforced
concrete beams of suspended, non-load-bearing ceilings
made of plasterboard, mineral fibre or wood wool plates
of types Knauf D11, D12, D13 and on AMF mineral fibre
ceilings or similar products with the same properties.
Suitable for vertical load due to a fall from height.
Maximum expected total deformation of the installation
base and the anchor point due to a fall from a height:
15 cm vertical. Adjust the length of the connector based on
conditions on site.
Installation:
This product may only be installed as per this instruction manual. MARK Save A Life GmbH recommends it is installed by
a specialist company.
3.3 Technical details
Installation base, components,
tools, operating conditions
Approved for Knauf systems or similar products
with the same properties
D11, D12, D13 and AMF mineral fibre ceilings
Test standard, permissible number of people
EN 795:2012, 1 person
Fasteners
2 x stainless-steel screws, countersunk head
M10x25
2 x deformation brackets
2 x Fischer FAZ II 12/10
4 x screws M8 x 25 8.8 galvanised
4 x washers 8.4 x 25 galvanised
2 x counterplates 2-hole
Drill
Masonry drill bit 12 mm
Screw-in depth
100 mm
Hole cutter
95 mm with centring drill 6 mm
Torque wrench
13 mm nut and 19 mm nut, Allen socket 6 mm
Tightening torques
M8: 27 Nm, M10: 20 Nm, M12: 60 Nm
Quality of the installation base
(static load-bearing capacity of the structure
must be guaranteed)
≥ C 20/25
Addition
Installation only on load-bearing ceilings or
beams made of reinforced concrete
Distance from edge
≥ 55 mm
Thickness of non-load-bearing cladding
(plasterboard, insulation)
1-3 layer cladding 12.5 mm/35 mm MF or WW
Permissible load directions
Vertical
Separation height
110 mm to 3000 mm
Maximum expected deformation due to a
fall from a height
≤ 150
Fig. Side view
8
9
Absorber B
UA profile J 75 mm
2. Measure the separation height of the suspended
ceiling (distance between lower edge of unfinished
ceiling and upper edge of suspended ceiling).
Cut UA profile
J
to this measurement.
1. Mark the position of anchor point
A
on the unfinished
ceiling. In the case of grid ceilings, in each case the
anchor point is positioned in the centre of the field of
a MF or WW plate.