7
EN
HMI-EC (06 99 150)
A2
Temp. sensor calibration
max. ±8°C with the step of 0.5°C
A3
Heating mode:
Heating [0], ventilation [1],
ventilation [2]
Selection [0, 1, 2]
A4
Hysteresis of differential
adjuster
0.5/1/2
A5
First speed value
15-80%
A6
Second speed value
15-90%
A7
Third speed value
15-100%
A8
Fan speed delay
30….200s
A9
Backlight time
5….600s
AA
Door optimum
0, +1, +2, +3
AB
Door sensor logic
NO [0], NC [1]
AC
Mim. Fan speed during cooling
down
45-100%
AD Min. fan speed
Only display
AE Calendar-based work
No [0], Yes [1]
AF Time mode
12h [1]; 24h [0]
B0 Buttons blockade
selection
B1 Extra heating time
0….90s
Bo Default settings
Hold
Note. The Door optimum function (AA) allows increase the fan
speed from currently set one in case of door opening:
‘’+1” –
increases the fan speed by one step when door is
open
‘’+
2
” –
increases the fan speed by two step when door is
open.
Anytime you ned to disable the
“Door optimum” function, just set it
to the
‘’+
0
”
setting.
.
6.2. ADVANCED SETTINGS, SECTION C
To enter the advanced settings C of this controller, press and
hold the [Set] button for 5 seconds at the deactivated controller.
Toggle between parameters using [Set] button. Change the value
or settings of selected parameters using [^] and [v] buttons. After
changes are applied, leave the settings mode by pressing power
button of the controller.
Your settings will be saved automatically. For advanced settings
A group, the following parameters can be modified:
No. Function
Set point
B0 Temperature units
°C/°F
B1 Min. Temperature
41 … 104
o
F (5
….
15 °C)
B2 Max. Temperature
61 … 104
o
F (16
….
40 °C)
B3 Communication Modbus
RTU
–
speed
2400/4800/9600 kbps.
B4 Communication Modbus
RTU
–
parity
None/ odd/ even
7. TECHNICAL SPECIFICATION
Power supply
o
1*90-240 VAC 50/60 Hz
Power consumption
o
1.5 VA
Features of the automatic action
o
Type 1 Action, Type 1.B Action (UL 60730-1)
Maximum current on relay outputs
o
5 A (max 2.5 A on each circuit)
Load type
o
Resistive, PF ≥ 0.95
RS485 port voltage / current limitation
o
-
7… +12V /
±250 mA
Temperature sensor type
o
NTC, NTC, 10 k
Ω
@ 77 °F (25 °C)
Measured temperature range
o
32 °F … 122 °F, (0 °C ... 50 °C)
Temperature measurement precision
o
±0.9
o
F (±0.5 °C)
Communication
o
Relay output: Dual - NO, 250 V, 5 A: 105 cycles, AgNi
@ 85 °C; 5 x 104 cycles, AgSnO2 @ 85 °C
o
Analog output: 0-10V (8 bit, Imax = 20 mA)
o
Modbus RTU, 2400/4800/9600 bps,
Working conditions limits
o
Temperature range: 32 °F … 122 °F (0 °C ... 50
°C)
o
Relative humidity: 10-90% with no condensation.
Storage conditions limits
o
Temperature range: -
4 °F … 122 °F (
-20 °C ... 50 °C)
o
Relative humidity: 10-90% with no condensation.
Ingress Protection
o
IP20
Maximum mechanical load on the controller installation
(flush mounting)
o
Parallel to the the wall, downwards, both sides: 5 N
o
Parallel to the the wall, upwards (front panel
unmounting direction), both sides: 2 N
o
Perpendicular to the wall: 5 N
Dimension
o
3-3/8" x 3-3/8" x 1-7/8" (86 x 86 x 48 mm)
Weight
o
5.3 oz (150 g).
8. NORMS AND STANDARDS