![Maritime Geothermal WH-Series Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/maritime-geothermal/wh-series/wh-series_installation-and-service-manual_1727436038.webp)
Page 38
002028MAN-01
1-Oct-2015
The following steps describe how to perform the startup of the heat pump.
The WH-Series Startup Record located in this manual is used in conjunction with this startup procedure to provide a detailed rec-
ord of the installation. A completed copy should be left on site, a copy kept on file by the installer, and a copy should be sent to Mari-
time Geothermal Ltd.
Check the boxes or fill in the data as each step is completed. For data boxes, circle the appropriate units. Fill in the top section of all
three copies, or one copy if photocopies can be made after the startup has been completed.
PRE-START INSPECTION
Indoor Loop (Hydronic Loop):
1.
Verify that all shutoff valves are fully open and there are no restrictions in the piping from the heat pump to the indoor loop,
and that full flow is available to the heat pump.
2.
Verify that the entire system has been flooded and all the air has been purged as much as possible.
Further purging may
be required after the system has been operating for a while.
3.
Verify that the loop contains the proper mix of antifreeze (if used) for the intended application. If applicable, record the type
of antifreeze and the mixture value on the startup sheet, circle % Vol. or % Weight.
4.
Record the static loop pressure on the startup sheet.
Outdoor Loop (Ground Loop):
1.
Verify that all shutoff valves are fully open and there are no restrictions in the piping from the heat pump to the ground loop,
and that full flow is available to the heat pump.
2.
Verify that the entire system has been flooded and all the air has been purged as much as possible.
Further purging may
be required after the system has been operating for a while.
3.
Verify that the loop contains the proper mix of antifreeze for the intended application. Record the type of antifreeze and the
mixture value on the startup sheet; circle % Vol. or % Weight.
4.
Record the static loop pressure on the startup sheet.
Outdoor Loop (Ground Water):
1.
Verify there are no leaks in the connections to the unit. Verify the water valve is installed and properly oriented in the
return line.
2.
Verify that there is flow control in the return line.
Electrical:
1. Ensure the power to the unit is off.
2.
Verify all high voltage connections. Ensure that there are no stray wire strands, all connections are tight, and the ground
wire is connected tightly to the ground connector.
3.
Record the circuit breaker size and wire gauge for the heat pump.
4.
Verify that the control connections to the unit are properly connected and all control signals are off, so that the unit will not start
up when the power is turned on.
5.
Verify that the circulator pumps are connected to the proper voltage terminals in the heat pump. Record the voltages of the
circulator pumps.
6.
Ensure all access panels except the one that provides access to the electrical box are in place.
Startup Procedure
Содержание WH-Series
Страница 9: ...1 Oct 2015 Page 9 002028MAN 01...
Страница 11: ...1 Oct 2015 Page 11 002028MAN 01...
Страница 12: ...Page 12 002028MAN 01 1 Oct 2015...
Страница 13: ...1 Oct 2015 Page 13 002028MAN 01...
Страница 16: ...Page 16 002028MAN 01 1 Oct 2015...
Страница 19: ...1 Oct 2015 Page 19 002028MAN 01...
Страница 43: ...1 Oct 2015 Page 43 002028MAN 01 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 56: ...Page 56 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 230 1 60...
Страница 57: ...1 Oct 2015 Page 57 002028MAN 01 ELECTRICAL DIAGRAMS 208 230 1 60 continued...
Страница 58: ...Page 58 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 220 1 50...
Страница 59: ...1 Oct 2015 Page 59 002028MAN 01 ELECTRICAL DIAGRAMS 220 1 50 continued...
Страница 60: ...Page 60 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 3 60...
Страница 61: ...1 Oct 2015 Page 61 002028MAN 01 ELECTRICAL DIAGRAMS 208 3 60 continued...
Страница 62: ...Page 62 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 380 3 50...
Страница 63: ...1 Oct 2015 Page 63 002028MAN 01 ELECTRICAL DIAGRAMS 380 3 50 continued...
Страница 64: ...Page 64 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 460 3 60...
Страница 65: ...1 Oct 2015 Page 65 002028MAN 01 ELECTRICAL DIAGRAMS 460 3 60 continued...
Страница 66: ...Page 66 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 575 3 60...
Страница 67: ...1 Oct 2015 Page 67 002028MAN 01 ELECTRICAL DIAGRAMS 575 3 60 continued...
Страница 68: ...Page 68 002028MAN 01 1 Oct 2015 REFRIGERATION CIRCUIT DIAGRAMS...
Страница 69: ...1 Oct 2015 Page 69 002028MAN 01 DIMENSIONS WH 25 45 55 DIMENSIONS WH 65 75 80...