002028MAN-01
1-Oct-2015
The following describes each item on the
Configuration Tab
of the
Configuration Page
.
IMPORTANT NOTE:
System setup is done at the factory. Normally, only the control source, optional alarms and fluid type / fluid mix
may need to be changed. Note that items that become unavailable or are automatic will be greyed out.
Model Configuration:
These are used to select the type of heat pump the control board is installed in.
Model Series:
Select the model series (refer to nameplate on unit) This will update remaining items to default values.
Model Size:
Select the model size (refer to nameplate on unit).
Model Function:
Select the model function (refer to the nameplate on the unit).
Refrigerant Type:
Select the refrigerant type (refer to the nameplate on the unit).
Number of Stages:
Select the number of stages (refer to the compressor model: ZP = 1 stage, ZPS = 2 stage).
EEV Step Range:
Automatically selected.
Jumper Configuration:
These are system level settings.
Control Source AIR:
Not Applicable.
Control Source HYD:
Select desired control source:
BACNet:
System is controlled via BACNet MS/TP RS-485 Interface. Refer to the
BACNet Interface
Section of the manual for more information.
Signals:
System is controlled via hardwired signals from an external source. Refer to the
Thermostat
Requirements
section of the manual for more information.
Setpoints:
System is controlled via on-board aquastat functionality. Refer to the
Setpoint Control
section of the manual for more information.
Setpoints Method:
Applicable only if
Setpoints
selected for
Control Source HYD
. Select
Indoor Loop
(default) for the
Indoor Circulator Sampling method or
HTS / CTS
to use external probes mounted in tanks.
Air/Hydronic Priority:
Not Applicable.
Number of Tanks:
Applicable only if
Setpoints
selected for
Control Source HYD
and
HTS / CTS
selected for
Setpoints
Method
. Select
One
for single tank systems or
Two
for systems with a hot and cold tank.
Fan En. For Hydronic:
Not Applicable.
Heat Pump / Chiller:
Not Applicable.
Fluid Selection:
Used to select the Indoor and Outdoor fluid types and volume mixture ratios.
Fluid Type (Outdoor):
Automatically Selected.
Fluid Mix (Outdoor):
Automatically Selected.
Fluid Type (Indoor):
Select appropriate fluid type to match the antifreeze type (or water) in the loop.
Fluid Mix (Indoor):
Select fluid mixture ratio (by volume). Greyed out if
Fluid Type
is water.
Pressure Cutouts:
Automatically Selected based on
Refrigerant Type
,
Fluid Type
and
Fluid Mixture
.
Alarm Controls:
These are optional or automatically selected alarms. If a button is greyed out and the Enabled
Indicator is on the alarm is automatic, if the Enabled Indicator is off then the alarm is not
available. Buttons that are not greyed out are optional alarms.
Outdoor Flow:
Not Applicable.
Indoor Flow:
Not Applicable.
Phase Monitor1:
Optional, for three-phase models only, requires Phase Monitor accessory.
Compressor Status1:
Optional, requires current sensor accessory.
Compressor Monitor1:
Not Applicable.
Содержание WH-Series
Страница 9: ...1 Oct 2015 Page 9 002028MAN 01...
Страница 11: ...1 Oct 2015 Page 11 002028MAN 01...
Страница 12: ...Page 12 002028MAN 01 1 Oct 2015...
Страница 13: ...1 Oct 2015 Page 13 002028MAN 01...
Страница 16: ...Page 16 002028MAN 01 1 Oct 2015...
Страница 19: ...1 Oct 2015 Page 19 002028MAN 01...
Страница 43: ...1 Oct 2015 Page 43 002028MAN 01 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 56: ...Page 56 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 230 1 60...
Страница 57: ...1 Oct 2015 Page 57 002028MAN 01 ELECTRICAL DIAGRAMS 208 230 1 60 continued...
Страница 58: ...Page 58 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 220 1 50...
Страница 59: ...1 Oct 2015 Page 59 002028MAN 01 ELECTRICAL DIAGRAMS 220 1 50 continued...
Страница 60: ...Page 60 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 208 3 60...
Страница 61: ...1 Oct 2015 Page 61 002028MAN 01 ELECTRICAL DIAGRAMS 208 3 60 continued...
Страница 62: ...Page 62 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 380 3 50...
Страница 63: ...1 Oct 2015 Page 63 002028MAN 01 ELECTRICAL DIAGRAMS 380 3 50 continued...
Страница 64: ...Page 64 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 460 3 60...
Страница 65: ...1 Oct 2015 Page 65 002028MAN 01 ELECTRICAL DIAGRAMS 460 3 60 continued...
Страница 66: ...Page 66 002028MAN 01 1 Oct 2015 ELECTRICAL DIAGRAMS 575 3 60...
Страница 67: ...1 Oct 2015 Page 67 002028MAN 01 ELECTRICAL DIAGRAMS 575 3 60 continued...
Страница 68: ...Page 68 002028MAN 01 1 Oct 2015 REFRIGERATION CIRCUIT DIAGRAMS...
Страница 69: ...1 Oct 2015 Page 69 002028MAN 01 DIMENSIONS WH 25 45 55 DIMENSIONS WH 65 75 80...