![Maritime Geothermal EMWT-65-HACW-P-1T Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/maritime-geothermal/emwt-65-hacw-p-1t/emwt-65-hacw-p-1t_installation-and-service-manual_1727430036.webp)
Page 36
000662MAN-03
01 MAR 2012
Model Specific Information
This section provides information particular to each model. For complete specifications please see the specifications docu-
ment for the desired model. The tables below depict the results of standard capacity rating tests according to C13256-2 stand-
ards. C13256-2 is identical to ISO13256-2.
Table 14 - Standard Capacity Ratings - Ground Loop Heating*
60Hz
EWT 104°F (40°C)
STAGE 1 - ELT 41°F (5°C)
STAGE 2 - ELT 32°F (0°C)
Model
Size
Liquid Flow
(Outdoor & Indoor)
Outdoor
Pressure Drop
Mode
Input
Energy
Capacity
COP
H
Tons
IGAL
USG
L/s
PSI
kPA
Watts
BTU/Hr
kW
W/W
65
5
12
14.4
0.91
5.3
36.3
Stage
1 3,370 37,600 11.0 3.27
Stage 2
4,380
45,800
13.4
3.07
75
6
14
16.8
1.06
6.0
41.4
Stage
1 3,905 45,600 13.3 3.42
Stage 2
4,740
51,400
15.1
3.18
* 15% NaCl by Weight Ground Loop Fluid
Table 15 - Standard Capacity Ratings - Ground Water Heating
60Hz
EWT 104°F (40°C)
ELT 50°F (10°C)
Model
Size
Liquid Flow
(Outdoor & Indoor)
Outdoor
Pressure Drop
Mode
Input
Energy
Capacity
COP
H
Tons
IGAL
USG
L/s
PSI
kPA
Watts
BTU/Hr
kW
W/W
65
5
12
14.4
0.91
4.5
31.2
Stage 1
3,390
42,900
12.6
3.71
Stage 2
4,545
58,800
17.2
3.79
75
6
14
16.8
1.06
4.9
33.5
Stage 1
3,860
52,200
15.3
3.96
Stage 2
4,860
66,300
19.4
4.00
STANDARD CAPACITY RATINGS
The tables below depict the results of standard capacity rating tests according to C13256-2, which is identical to ISO13256-2.
Stage 1 values do not apply to single stage units. Refer to the
Electrical Tables
to determine which models are single stage.
NOTE: Due to the setup of this series of heat pumps, there is no actual reversing mode, the values in the cooling tables are
what would be obtained when operating at the given conditions.
This section provides general information particular to each model. For complete specifications please see the specifications
document for the desired model.
Table 12 - Refrigerant - R410a
SIZE
Lbs.
kg
65
8.0 3.6
75
9.0 4.1
System contains POE oil.
REFRIGERANT CHARGE CHART
SHIPPING INFORMATION
Table 13 - Shipping Information
MODEL
WEIGHT
DIMENSIONS in (cm)
Lbs. (kg)
L
W
H
65
TBD
86 (218)
36 (91)
48 (122)
75
1100 (499)
86 (218)
36 (91)
48 (122)
Содержание EMWT-65-HACW-P-1T
Страница 9: ...01 MAR 2012 Page 9 000662MAN 03...
Страница 10: ...Page 10 000662MAN 03 01 MAR 2012...
Страница 13: ...01 MAR 2012 Page 13 000662MAN 03...
Страница 16: ...Page 16 000662MAN 03 01 MAR 2012...
Страница 19: ...01 MAR 2012 Page 19 000662MAN 03...
Страница 34: ...Page 34 000662MAN 03 01 MAR 2012 REFRIGERATION CIRCUIT DIAGRAM...
Страница 35: ...01 MAR 2012 Page 35 000662MAN 03 REFRIGERATION CIRCUIT DIAGRAM continued...
Страница 41: ...01 MAR 2012 Page 41 000662MAN 03 ELECTRICAL DIAGRAMS 230 1 60...
Страница 42: ...Page 42 000662MAN 03 01 MAR 2012 ELECTRICAL DIAGRAMS 230 1 60 continued...
Страница 43: ...01 MAR 2012 Page 43 000662MAN 03 Back View Front View CASE DETAILS Right Side View...