67
22 Position Terminal Block
Functions
A. Provides 6 sets of programmable contacts at pin 1 thru pin 18 for intersection flash control, Remote
Alarms, Pagers or other user interface.
1. “Low Batt”: batteries have reached approximately 40% capacity remaining
2. “On Batt”: unit is in inverter mode
3. “Timer”: unit has been in inverter mode for 2 hours (programmable)
4. “Alarm”: any of the following conditions occur:
a. Any alarm
b. Line freq. un-match
c. Output under voltage
d. Temp. Probe disconnect
e. Over load
f. Batt. Not Connect
g. Batt Hi Temp. > +60 Deg C
h . Batt Hi Temp. < -15 Deg C
5. “Fault”: any of the following conditions occur:
a. Any fault
b. Short circuit
c. Battery under voltage
d. Battery over voltage
e. Battery over temperature
g. Over load
B. Provides 24VDC (TRTC-0654-N1/N2, TRTC-1124-N1/N2, / 48VDC (TRTC-2005-N1/N2) signal to PTS
on pins 21 & 22
C. Provides programmable input contact on pins 19 & 20.
1. Self-test
2. EXT. Alarm
3. EXT. BATT Alarm
4. EXT. FAN Alarm
5. DOOR INTERLOCK
Contact Type
Form C. Dry contacts rated 1 Amp at 240V
Wiring
Uses 14-26 AWG
Communication Specifications
RS-232/USB/Ethernet
ports
Monitors, controls and calibrates with terminal emulation software for service personnel to obtain unit
diagnostics
RS-232
DB-9, Female, Opto-Isolated, straight-thru cable
USB
B-Type receptacle
Ethernet (optional)
10/100 Mbps Ethernet, auto-detected
Display Panel
4-line LCD
Note:
De-rate operating temperature above 4900 ft (1500m) by 2°C per 1000 ft (300m).
Due to ongoing product improvements, specifications are subject to change without notice.