66
2.4.5 Specifications
Functions
Brownout Protection
This unit boosts the output voltage (or transfers
to Battery) during Brownout or Low input line
conditions and returns to Normal when input
power stabilizes and returns to Normalcy.
These values for Transfer / Retransfer, To /
From Battery / Boost mode are user
programmable
Generator
Compatibility
Generator mode allows for more variations in
input voltage and frequency for use with an AC
generator
Battery Charger 10A
PFC switch-mode charger is temperature-
compensated (-2.5 to
-5 mV/C/Cell) with automatic shut off
above 50 deg C
Inverter Mode
Capable of running continuously in
inverter mode
Inverter Mode Current
Limit
Continuous electronic current limit is
provided
Measurements
available for remote
monitoring
- Input and output voltages
- Input line frequency
- Battery voltage and current
- Battery and heat sink temp
Mechanical Specifications
Dimensions
(H x W x D)
TRTC-0654-N1/N2, TRTC-1124-N1/N2:
88.6 mm x 432 mm x 254 mm 2U
3.5” x 17.0” x 10”
TRTC-2005-N1/N2:
133 mm x 432 mm x 254 mm 3U
5.3” x 17.0” x 10”
Weight
TRTC-0654-N1/N2, TRTC-1124-N1/N2:
13 kg / 29 lbs
TRTC-2005-N1/N2:
21 kg / 46 lbs
Input Connection
3 Position Terminal Block OR
Anderson PP45 Quick connector OR
IEC socket
Output Connection
3 Position Terminal Block OR
Anderson PP45 Quick connector OR
IEC socket
Mounting
19” (483 mm) or 23” (584 mm) rack/shelf mount
Cooling (Ext. Fan)
Microprocessor controlled, DC Fan
TRTC-0654-N1/N2, TRTC-1124-N1/N2:
24VDC, TRTC-2005-N1/N2: 48VDC
Audible Noise Level
<40 dBA
Operating Temperature
-37° C to + 74°C / -35° F to +165° F
Storage Temperature
-50° C to + 75°C / -58° F to +167° F
Humidity
Less than or equal to 95%, Non-Condensing
Altitude
10,000 ft / 3048 meters (See Note 1)
Electrical Specifications
Output Apparent Power
TRTC-0654-N1/N2: 650VA
TRTC-1124-N1/N2: 1100VA
TRTC-2005-N1/N2: 2000VA
(Inverter Mode)
2000VA (Line Mode)
Output Active Power
Inverter Mode and
Line Mode
TRTC-0654-N1/N2: 650W
TRTC-1124-N1/N2: 1100W
TRTC-2005-N1/N2: 2000W
Power Factor
1.0
Input Frequency
+/- 3Hz
120V: 60Hz
220/230/240V: 50/60Hz
Input Voltage Range
120V: 90 to 150 VAC
User programmable
220V: 168 to 275 VAC
User programmable
230V: 175 to 287 VAC
User programmable
240V:183 to 300 VAC
User programmable
Output Voltage
Inverter Mode
120/220/230/240 VAC
(Tolerances are User programmable)
120/220/230/240 VAC+/-5%
Maximum Input Current
120V:
TRTC-0654-N1 / TRTC-1124-N1: 20A
TRTC-2005-N1: 30A
220/230/240V:
All Models: 20A
Transformer
Linear (Non-Isolated)
Transfer Time, msec
<65
Inrush Current
Load Dependent
Output Waveform THD
< 3 % (Resistive Load)
Load Crest Ratio
3:1
Efficiency, Line Mode
> 95% (Resistive Load)
Efficiency, Inverter Mode
> 80% (Resistive Load)
Nominal Battery
String Voltage
TRTC-0654-N1/N2: 24VDC
TRTC-1124-N1/N2: 24VDC
TRTC-2005-N1/N2: 48VDC
Step Load Response
1 Cycle Full recovery.
Over current Protection
Single pole circuit breaker for input
120VAC:
TRTC-0654-N1 / TRTC-1124-N1: 20A
TRTC-2005-N1: 30A
220/230/240 VAC:
All Models: 20A
DC Bus:
TRTC-0654-N1/N2 & TRTC-1124-N1/N2:
60Amp Circuit Breaker.
TRTC-2005-N1/N2
90Amp Circuit Breaker
DC Power
Drawn from batteries