i
STANDARD RUN-TIME MODELS
GENERAL
Rated Capaci
ty: 6
00VA, 1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.
6
Technology:
L
ine
-interactive
topology with
true sinewave output on battery
INPUT
Phase:
Single phase plus ground
Input
Voltage
s: 110V, 115V, 120V or 220V, 230V, 240V
Input Voltage Range: ± 25%
Frequency:
50 / 60 Hz
a
uto sensing
AC Frequency
R
ange:
45 - 65 Hz
Input Current (120V): 600VA - 5A, 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A, 3000VA -25A
Input Current
(230V): 600VA - 2.6A, 1000VA - 4.4A, 1500VA - 6.5A, 2000VA - 8.7A, 3000VA - 13A
Input Protection: Fuse or circuit breaker for overload and short circuit (model dependent)
DC Bus Voltage: 600VA - 24V, 1000VA - 24V, 1500VA - 36V, 2000VA - 48V, 3000VA - 96V
OUTPUT
Output Voltage:
110V, 115V, 120V or 220V, 230V, 240V
Voltage
R
egulation:
±
5
%
(600VA - 3000VA)
Voltage
D
istortion
: <
5% THD with non-linear loads, < 3% THD with linear loads
Frequency
R
egulation
:
± 0.
5%
(while on battery
)
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
or increases by between 9% and 25%
Transfer Time
:
Between 4 and 8 milliseconds including detection time
Efficiency (
Standby
Mode):
Greater than
95
%
Overload Capacity: 110% for 20 seconds, 125% for 5 seconds
EXTENDED RUN-TIME MODELS
GENERAL
Rated power:
1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor of 0.
6
Technology:
Line-interactive topology with true sinewave output on battery
INPUT
Phase:
Single phase plus ground
Input Voltages: 110V, 115V, 120V or 220V, 230V, 240V
Input Voltage Range: ± 25%
Frequency:
50 / 60 Hz
a
uto-sensing
AC Frequency
R
ange:
4
5 - 65 Hz
Input Current (120V): 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A, 3000VA -25A
Input Current
(230V)
:
1000VA - 4
.4
A, 1500VA -
6.
5A, 2000VA -
8
.7A, 3000VA - 1
3
A
Input Protection: Fuse or circuit breaker for overload and short circuit (model dependent)
DC Bus Voltage: 1000VA - 24V, 1500VA - 36V, 2000VA - 48V, 3000VA - 48V
OUTPUT
Output Voltage:
110V, 115V, 120V or 220V, 230V, 240V
Voltage
R
egulation:
± 5% (1000VA - 3000VA)
Voltage
D
istortion:
< 5% THD with non-linear loads, < 3% THD with linear loads
Frequency
R
egulation
:
± 0.5
%
(while on battery)
Automatic Voltage Regulation: Increases or decreases output voltage by 15% if the input voltage decreases
or increases by between 9% and 25%
Transfer Time: Between 4 and 8 milliseconds including detection time
Efficiency
(Standby Mode): Greater than 95%
Overload Capacity: 110% for 20 seconds, 125% for 5 seconds
14. Specifications