4. Installation
4.1 Inspection
Inspect the UPS upon receipt for any visible damage. The packaging is recyclable; save it for reuse
or dispose of it properly.
NOTE: If the power consumption of the load is listed in units other than VA (e.g., Watts), use the
following calculations for conversion:
______ Watts(W) x 1.67 = ______ VA OR 120V x ______ Amps(A) = ______ VA
4.2 Placement
Install the UPS in a protected area with adequate airflow and free of excessive dust.
CAUTION:
Do NOT operate the UPS where the temperature and humidity is outside the specified
limits.
4.3 Telephone / Modem Line Connection
Connect a single line telephone or a modem line to the telephone/modem surge protection sockets
on the rear of the UPS. The RJ-45 modular sockets accept standard single line telephone
connectors. This connection requires an additional length of telephone cable (supplied).
CAUTION:
The telephone/modem line connection is optional and not necessary for the UPS to
function correctly.
NOTE: The telephone line current limiting feature may be rendered inoperable if improperly
installed. Make sure that the telephone line from the wall is plugged into the connector labeled “IN”,
and the device to be protected (telephone, modem, etc.) is plugged into the connector labeled “OUT”.
NOTE: This surge protection device is for indoor use only. Never install telephone wiring during a
lightning storm.
4.4 Power Source Connection
4.41 Cord connected models
Connect the AC power cord to a properly wired and grounded outlet to energize the UPS
4.42 Hardwired models
The terminal block is used to “hardwire” the UPS, thus allowing connection of input/output wiring.
Use #8 AWG wire (Twisted wire cable) for possible 3/4” conduit use and terminate each wire with
appropriate size/rating terminal lugs. Input/Output wires should be secured with terminal block
screws using 29 ft.-lbs. of torque.
4.5 Battery Charging
The UPS charges its battery whenever it is connected to utility power. For optimum results, charge
the battery for at least 6 hours prior to initial use.
4.6 Load Connection
Plug the load(s) into the output receptacles or connect them to the hard-wired terminal block on
the rear of the UPS. To use the UPS as a master ON/OFF switch, make sure all of the loads are
switched ON.
CAUTION:
Do NOT connect a laser printer or plotter to the UPS with other computer equipment.
A laser printer or plotter periodically draws significantly more power than when idle, and may
overload the UPS. (Does not apply to some models which may be oversized to accomodate such).
8
!
!