6.  Appendix A - Troubleshooting 

 

PROBLEM 

CAUSE 

CORRECTIVE ACTION 

If UPS does 

not turn ON 

 

(OR) 

 

LED does not 

Illuminate 

 

ON/OFF/TEST/SILENCE button not 

pushed or push-time too short 

Press the ON/OFF/TEST/SILENCE button 

more than 1 second 

Battery voltage less than 10V 

Recharge the UPS for at least 6 hours 

PCB failure 

Replace the PCB, call for service 

Load less than 40W in battery mode 

Normal condition, “No load shutdown function” 

is active 

UPS always in 

battery mode 

Loose AC input connection  

Recheck input connection   

Blown input AC fuse 

Replace the AC fuse 

Line voltage too high, too low or AC power 

failure 

Normal condition 

PCB failure  

Replace PCB, call for service 

Back up time 

too short 

Battery not fully charged 

Recharge the UPS at least 6 hours 

PCB failure 

Replace PCB, call for service 

Buzzer beeps 

continuously 

Output Overload 

Remove some loads 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание SDRS-0300-H1

Страница 1: ...DIN Rail Uninterruptible Power System User Manual for Models SDRS 0300 H1 SDRS 0300 H2 SDRS 0500 H1 SDRS 0500 H2 300W 500W...

Страница 2: ...2...

Страница 3: ...3 Table of Contents Section Page Safety Instructions 4 Introduction 4 1 Presentation 5 2 Installation 6 3 Operation 7 4 Alarm 7 5 Software 8 6 Troubleshooting 9 7 Specifications 10 8 Warranty 11...

Страница 4: ...onnect charging source prior to connecting or disconnecting battery terminals CAUTION Risk of Electric Shock UPS equipment outputs remain live with main disconnect in off position Battery replacement...

Страница 5: ...ion c If the unit shuts down due to overload the LED and alarm will continue for two minutes 3 BATTERY MODE Indicator Yellow LED The LED will illuminate when the UPS is supplying battery power to the...

Страница 6: ...serviceable parts Hazardous live parts inside this unit are energized from the battery supply even when the input AC power is disconnected 2 3 Utility power The terminal block is used to hardwire the...

Страница 7: ...operation the alarm would stop Attention In the BACKUP mode the alarm will beep every 2 seconds Slow speed beep Attention The UPS provides mute function for this warning When the beeping sound occurs...

Страница 8: ...ignals which the individual system recognizes The interface cable from the UPS end must be connected to a REMOTE PORT on the computer end It can be either be COM 1 or COM 2 For other installation inst...

Страница 9: ...e PCB call for service Load less than 40W in battery mode Normal condition No load shutdown function is active UPS always in battery mode Loose AC input connection Recheck input connection Blown input...

Страница 10: ...10 seconds 130 at 3 seconds Short circuit protection UPS output cut off immediately BATTERY Type Sealed maintenance free lead acid battery Battery quantity 12V 7 2Ah x 1 12V 9Ah x 1 Typical recharge...

Страница 11: ...ied values They are not intended to function as surge arrestors The UPS is intended to be installed on the load side of the service entrance and has been tested to verify that transient voltage surges...

Страница 12: ...hon Power Inc 2020 MP_DIN Rail User Manual_Jul_2020 Marathon Power Inc 2020 2538 E 54th Street Huntington Park CA 90255 Office 310 689 2328 Fax 310 689 2329 support marathon power com www marathon pow...

Отзывы: