ME697 (Eagle version) 

 

Page 4 

 

 

 

INSTALLATION GUIDE 

for 

ME697 Interface Card 

 

with 

MES20 and other flowmeters 

 

(1) Locate the most appropriate position to mount the MES20 flowmeter. Preferably: 

 your site’s flowmeters should be grouped together off the ground on a stand.  

 protect the flowmeters from the elements by using a cover, which should be lightweight with handles for easy access 

by service personel. 

 a vibration free area is recommended, as the MES20 is sensitive to high vibrations which can cause some stray 

pulses (see the “Installation” section in the MES product brochure). 

 

(2) Establish the outlet point position in relation to the storage tank: 

2a) If the outlet point is above the top of the storage tank (the most commonly used setup)

, then 

the equipment you will need is at least: a pump, non-return valves or spring loaded check valves (12psi), flow 
restriction gate or ball valve, a flowmeter with pulse output and, optionally: 

 a solenoid valve (air-assisted ball valve type) for instant shut off of flow, recommended to prevent the Venturi effect 

when injecting into water lines, but may not be required if the installation has reasonable head height.  

 a 3-Way Valve to provide an easily accessible calibration point. 

ADMIX

STORAGE

TANK

PUMP

Gate Valve 
restricts flow

Filter

Non-Return

Valve

tank

Valve

Flowmeter

Non-Return Valve

optional 3-Way Valve 
(calibration point)

optional Solenoid – to
prevent Venturi effect 
if injecting into 
water lines.

outlet line 
above level of
Storage Tank
(most common)

ME697

Contactor

 

 

2b)

 

If the outlet point is at the same level as the storage tank

, then the equipment you will need is at least: a pump, 

a flow restriction gate or ball valve, a flowmeter with pulse output, and a solenod valve to stop free flow. 

ADMIX

STORAGE

TANK

PUMP

Gate Valve 
restricts flow

Filter

Non-Return

Valve

tank

Valve

Flowmeter

Non-Return 
Valve

optional 3-Way Valve 
(calibration point)

Solenoid

outlet line 
at same level as
Storage Tank

ME697

Contactor

 

 

2c)

 

If the outlet point is below the level of the storage tank

, then the equipment you will need is at least: a flow 

control solenoid valve, a flow restriction gate or ball valve, and a flowmeter with pulse output. 

ADMIX

STORAGE

TANK

Gate Valve 

restricts flow

Filter

tank

Valve

Flowmeter

outlet line 
below level of
Storage Tank

ME697

Solenoid

an optional pump 

may be used to 

speed up flowrate

PUMP

 

Содержание ManuFlo ME697

Страница 1: ...d by individual channel LCD displays in millilitres The pulses are then sent to the computer inputs yellow Opto22 When the computer system has OPTO22 110 240 vac input optos incoming pulses are limited to 14 Hz maximum Due to high resolution pulsing of flowmeters the pulse rates must be divided The onboard selectable dip switches are then set to the desired pulse division rate see Fig 1 The divide...

Страница 2: ...ng on ME697 card from the computer supply Do not mix active pump drive with computer s Uninteruptable Power Supply UPS NOTE Neutral J2 and J5 is already bridged internally J5 active line after switch and fuse is bridged to J1 Active and J3 Active Only wire A N E J5 power input plug Six wires from J1 to computer yellow Opto22 pulses Seven wires from J2 to computer black Opto22 six start drives one ...

Страница 3: ... 8 of Connector J2 If there is still a problem then it is a Computer issue that the master reset is stuck on Disconnect the plug connecting the Computer to J2 and batch manually if the batching computer s black Optos are leaky i e there is more than 60vac residual voltage after Opto latches off which could cause batching to continue because the ME697 relay is being held on then o replace the Black...

Страница 4: ...s but may not be required if the installation has reasonable head height a 3 Way Valve to provide an easily accessible calibration point ADMIX STORAGE TANK PUMP Gate Valve restricts flow Filter Non Return Valve tank Valve Flowmeter Non Return Valve optional 3 Way Valve calibration point optional Solenoid to prevent Venturi effect if injecting into water lines outlet line above level of Storage Tan...

Страница 5: ...ME697 Eagle version Page 5 A ...

Страница 6: ...ME697 Eagle version Page 6 ...

Страница 7: ...ER SUPPLY to card 1A 240 vac power supply 1B 110 vac power supply 1C 24 vac power supply 1D 24 VDC power supply START INPUT DRIVES and MASTER RESET from Computer starts 2A 240 vac power supply 2B 110 vac power supply 2C 24 vac power supply 2D 24 VDC power supply START OUTPUT DRIVES from ME697 to contactor coils and solenoids 3A 240 vac power supply 3B 110 vac power supply 3C 24 vac power supply 3D...

Отзывы: