ME697 Troubleshooting 

 

• keep input rate to AC Computer/PLC below 15 Hz (otherwise overdose could occur due to computer missing pulses). 
 
• if the ME697 appears disabled (e.g. displays read zero, does not count, no functions even in manual mode) then the 

Master Reset black Opto on the PLC is leaking, or is stuck on causing a continual reset drive to the ME697. 
Measure the leakage voltage between the Master Reset (Connector J2, pin 7) and Neutral (Connector J2, pin 8). If 
there is more than 60vac voltage, then: 

o

 

replace the Black Optos; and/or 

o

 

fit a 12-15 K

 10W resistor between the Master Reset and Neutral (i.e. between pins 7 and 8 of Connector J2). 

If there is still a problem, then it is a Computer issue that the master reset is stuck on. Disconnect the plug connecting 
the Computer to J2 and batch manually. 

 

 

if the batching computer’s black Optos are leaky (i.e. there is more than 60vac residual voltage after Opto latches off, 
which could cause batching to continue because the ME697 relay is being held on), then: 

o

 

 replace the Black Optos; and/or 

o

 

 fit a 12-15 K

 10W resistor between each black Opto’s Active 240vac Computer Start (i.e. relevant pin on 

connector J2) and Neutral (pin 8 on Connector J2). 

 
• if experiencing slow counts on one channel after batch completes: ensure that Check Valve is not faulty. 
 
• if experiencing phantom counts on one channel: check wiring and shield. 
 

 

if experiencing constant phanton counts on many channels: the internal 1000 

μ

F electrolytic capacitor may have 

failed, so return the ME697 to ManuFlo for service.

Содержание ManuFlo ME697

Страница 1: ...d by individual channel LCD displays in millilitres The pulses are then sent to the computer inputs yellow Opto22 When the computer system has OPTO22 110 240 vac input optos incoming pulses are limited to 14 Hz maximum Due to high resolution pulsing of flowmeters the pulse rates must be divided The onboard selectable dip switches are then set to the desired pulse division rate see Fig 1 The divide...

Страница 2: ...ng on ME697 card from the computer supply Do not mix active pump drive with computer s Uninteruptable Power Supply UPS NOTE Neutral J2 and J5 is already bridged internally J5 active line after switch and fuse is bridged to J1 Active and J3 Active Only wire A N E J5 power input plug Six wires from J1 to computer yellow Opto22 pulses Seven wires from J2 to computer black Opto22 six start drives one ...

Страница 3: ... 8 of Connector J2 If there is still a problem then it is a Computer issue that the master reset is stuck on Disconnect the plug connecting the Computer to J2 and batch manually if the batching computer s black Optos are leaky i e there is more than 60vac residual voltage after Opto latches off which could cause batching to continue because the ME697 relay is being held on then o replace the Black...

Страница 4: ...s but may not be required if the installation has reasonable head height a 3 Way Valve to provide an easily accessible calibration point ADMIX STORAGE TANK PUMP Gate Valve restricts flow Filter Non Return Valve tank Valve Flowmeter Non Return Valve optional 3 Way Valve calibration point optional Solenoid to prevent Venturi effect if injecting into water lines outlet line above level of Storage Tan...

Страница 5: ...ME697 Eagle version Page 5 A ...

Страница 6: ...ME697 Eagle version Page 6 ...

Страница 7: ...ER SUPPLY to card 1A 240 vac power supply 1B 110 vac power supply 1C 24 vac power supply 1D 24 VDC power supply START INPUT DRIVES and MASTER RESET from Computer starts 2A 240 vac power supply 2B 110 vac power supply 2C 24 vac power supply 2D 24 VDC power supply START OUTPUT DRIVES from ME697 to contactor coils and solenoids 3A 240 vac power supply 3B 110 vac power supply 3C 24 vac power supply 3D...

Отзывы: