MANTION SMT Adresse postale : 2 rue des Métiers 21110 Genlis
Tél. : (33) 03 80 37 85 71 Fax : (33) 03 80 37 88 61
18
230V wired version
The installation must be equipped (L, N) with a two-pole external circuit-breaker (or selector switch)
on the primary side, in order to isolate the product if necessary.
Recommended external protection: Thermal magnetic circuit-breaker 4A, curve C or equivalent
1 Connect the second motor to the "Motor 2" connector with the 2 x 0.5 cable, matching the
colours of the wires already connected to the connector. (Blue on blue and brown on brown).
Only for the two-shutter version. For the single shutter version (left or right), this cable does not exist.
2 Connect the switch.
3 Connect the power supply.
For your safety: check that the installation is powered down when connecting.
Terminals
Phases
Colour
L
Phase
Brown
N
Neutral
Blue
Earth
Yellow/Green
230V
AC
± 15%
(196V
AC
–
264V
AC
),
50/60Hz +
Earth
Green
opening
White
common
Brown
closing
Pull down keys of the switch to
make the connection
realized a bridge
with a 0.5mm²
wire