![MANN+HUMMEL TRI-KLEEN 500 UV BR Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/mann-hummel/tri-kleen-500-uv-br/tri-kleen-500-uv-br_instruction-manual_701601006.webp)
2
atmospheres may require the use of intrinsically safe equipment, specific engineering controls, and personal
protective equipment (PPEs) in accordance with Occupational Safety and Health Administration (OSHA),
Environmental Protection Agency (EPA), and other federal, state, provincial and local regulations.
GENERAL INFORMATION
The TRI-KLEEN portable air filtration units incorporate the HEPA (High Efficiency Particulate Air) filtration which provides
the most effective available mechanical filtration method. In addition to providing HEPA filtration, the units are
primarily used in a negative pressure or recirculation mode. A negative pressure condition is created in order to confine
contaminated airborne particles. This condition exists when the static pressure inside the room containing the unit(s) is
lower in relation to the pressure of the environment outside the room. The static pressure differential is created and
maintained by continuously exhausting air out of a given room at a faster rate than air enters the room from all other
sources. In the recirculation mode, all or part of the filtered air is exhausted back into the room containing the unit.
The TRI-KLEEN portable air filtration units can be used to create a positive pressure condition by directing filtered
exhaust air from the units to another area of the facility via rigid or flexible ducting; however, this is not their primary
application. A positive pressure condition exists when the static pressure in a given room is higher relative to the
pressure of the environment outside the room. The static pressure differential is created and maintained by
continuously delivering air into a given room at a faster rate than air is exhausted from the room.
TRI-KLEEN 500UV BR includes four ultraviolet germicidal irradiation UVGI (hereinafter referred to as UV) lamps that
irradiate the air flowing through the unit. The lamp is affixed to the inside of the HEPA filter base and emits germicidal
ultraviolet light that inhibits the growth of bacteria and viruses. UV capability can only be integrated by the factory at
the time of order and it cannot be added after the machine is manufactured.
Содержание TRI-KLEEN 500 UV BR
Страница 1: ...TRI KLEEN 500 UV BR PORTABLE AIR FILTRATION UNITS ...
Страница 2: ...INSTRUCTION MANUAL ...
Страница 24: ...20 ...