86
Part Number STH044 10/13
LOW PRESSURE CUTOUT (LPCO) CONTROL
FUNCTION
Stops the ice machine if the low side pressure is too
low. The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint.
CHECK PROCEDURE
1. Connect manifold gauge set to suction access
valve.
2. Disconnect wires from low pressure switch and
connect ohm meter across LPCO terminals.
Replace the LPCO control if it:
1. Is not closed at the specified setpoint.
2. Does not open at the specified setpoint.
Specifications
Cut-Out
Cut-In
Current Production &
Replacement Part
17 psig ±5
35 psig ±7
Содержание RNS012
Страница 2: ......
Страница 8: ......
Страница 26: ...18 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 32: ...24 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 48: ...40 Part Number STH044 10 13 9 Lift out ice damper ...
Страница 49: ...Part Number STH044 10 13 41 10 Lift out ice strainer ramp ...
Страница 50: ...42 Part Number STH044 10 13 11 Turn ice wiper counterclockwise to remove ...
Страница 53: ...Part Number STH044 10 13 45 16 Remove three thumbscrews then remove bin cover REMOVE THUMBSCREWS ...
Страница 56: ...48 Part Number STH044 10 13 19 Remove ice dispensing wheel by lifting straight out ...
Страница 57: ...Part Number STH044 10 13 49 20 Water Reservoir Cover Removal A Push up on cover to snap off ...
Страница 62: ...54 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 109: ...Part Number STH044 10 13 101 SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING USING PINCH OFF TOOL ...
Страница 110: ...102 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 116: ...108 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 122: ...114 Part Number STH044 10 13 This Page Intentionally Left Blank ...
Страница 123: ......