212
Part Number STH026 2/12
CLEANUP PROCEDURE
Mild System Contamination
1. Replace any failed components.
2. If the compressor is good, change the oil.
3. Replace the liquid line drier.
NOTE:
If the contamination is from moisture, use
heat lamps during evacuation. Position them at the
compressor, condenser and evaporator prior to
evacuation. Do not position heat lamps too close to
plastic components, or they may melt or warp.
4. Follow the normal evacuation procedure, except
replace the evacuation step with the following:
A. Pull vacuum to 1000 microns. Break the
vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig
(35 kPa,.35 bar).
B. Pull vacuum to 500 microns. Break the
vacuum with dry nitrogen and sweep the
system. Pressurize to a minimum of 5 psig
(35 kPa,.35 bar).
C. Change the vacuum pump oil.
D. Pull vacuum to 500 microns. Run the vacuum
pump for 1 hour.
NOTE:
You may perform a standing vacuum test to
make a preliminary leak check. You should use an
electronic leak detector after system charging to be
sure there are no leaks.
5. Charge the system with the proper refrigerant to
the nameplate charge.
6. Operate the ice machine.
Important
Dry nitrogen is recommended for this procedure.
This will prevent CFC release.
Indigo_Model_Tech.book Page 212 Monday, February 20, 2012 1:17 PM
Содержание QuietQube Indigo Series
Страница 2: ......
Страница 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Страница 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Страница 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Страница 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Страница 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Страница 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Страница 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Страница 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Страница 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Страница 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Страница 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Страница 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 247: ......