HARVEST CYCLE DIAGNOSTICS QUIETQUBE ®
REMOTE CONDENSING UNIT
The headmaster control valve diverts the compressor
discharge gas to the ice machine receiver in the
harvest cycle. All refrigerant flow through the
condenser in the harvest cycle stops. Symptoms of a
headmaster valve that will not seat 100% closed
(completely bypass the condenser) in the harvest
cycle are:
•
Freeze cycle suction and discharge pressure are
normal.
•
The control board indicates safety limit #2. The
failure seems to be temperature related. Example:
The ice machine may function correctly at
temperatures above 32°F but fails at temperatures
below 32°F.
•
Harvest cycle suction pressure is low.
•
Harvest cycle discharge pressure is normal or
slightly low.
Procedure
1. Freeze cycle operation must be normal before
diagnosing the headmaster in the harvest cycle.
(Refer to Cycle Times/24 hr Ice Production/
Refrigerant Pressure Chart)
2. Allow the ice machine to run a normal freeze
cycle (do not initiate an early harvest cycle).
3. At the start of the harvest cycle feel the
compressor discharge line and the liquid line to
the ice machine receiver at the headmaster valve.
The temperature of both lines will be highest at
the beginning of the harvest cycle and then
decrease. Compare the lines 30 seconds into the
harvest cycle and then refer to Harvest Cycle
Headmaster Control Valve Failure List page 198.
Indigo_Model_Tech.book Page 202 Monday, February 20, 2012 1:17 PM
Содержание QuietQube Indigo Series
Страница 2: ......
Страница 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Страница 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Страница 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Страница 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Страница 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Страница 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Страница 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Страница 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Страница 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Страница 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Страница 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Страница 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 247: ......