HARVEST SEQUENCE
5.
Water Purge
The air pump(s) (when used) and the harvest valve(s)
open at the beginning of the water purge to divert
refrigerant gas into the evaporator.
The water pump continues to run, and the water dump
valve energizes to purge the water in the water trough.
ICVD Condensing Unit:
When the refrigerant pressure is low enough to open
the fan cycling pressure control the condenser fan
motor stops.
6.
Harvest
The air pump(s) (when used) remains energized and
the harvest valve(s) remains open. The refrigerant gas
warms the evaporator causing the cubes to slide, as a
sheet, off the evaporator and into the storage bin.
Single evaporator models
- The sliding sheet of
cubes opens the water curtain/ice damper and bin
switch.
The momentary opening and re-closing of the bin
switch will terminate the harvest sequence and return
to the freeze sequence (Step 3 - 4.)
Twin evaporator models
- The sliding sheet of cubes
opens the ice damper and bin switch. The momentary
opening and re-closing of the bin switch de-energizes
the harvest valve for the evaporator. When all of the
bin switches have opened and closed the ice machine
will terminate the harvest sequence and return to the
freeze sequence (Step 3 - 4.)
Indigo_Model_Tech.book Page 105 Monday, February 20, 2012 1:17 PM
Содержание QuietQube Indigo Series
Страница 2: ......
Страница 22: ...22 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 36: ...36 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 60: ...60 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 110: ...110 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 115: ...Part Number STH026 2 12 115 This Page Intentionally Left Blank ...
Страница 116: ...116 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 157: ...Part Number STH026 2 12 157 This Page Intentionally Left Blank ...
Страница 158: ...158 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 197: ...Part Number STH026 2 12 197 This Page Intentionally Left Blank ...
Страница 209: ...Part Number STH026 2 12 209 This Page Intentionally Left Blank ...
Страница 216: ...216 Part Number STH026 2 12 USING PINCH OFF TOOL ...
Страница 220: ...220 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 233: ...Part Number STH026 2 12 233 I0670C I0870C I1070C I1270C QuietQube Remote Air cooled 1 3 Ph ...
Страница 234: ...234 Part Number STH026 2 12 IB0690C IB0890C IB1090C QuietQube Remote Air cooled 1 3 Ph ...
Страница 235: ...Part Number STH026 2 12 235 II1400 I1800 I2170 QuietQube Remote Air cooled 1 3 Ph ...
Страница 236: ...236 Part Number STH026 2 12 ICVD2095 QuietQube Remote Air cooled 3 Ph ...
Страница 243: ...Part Number STH026 2 12 243 This Page Intentionally Left Blank ...
Страница 244: ...244 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 245: ...Part Number STH026 2 12 245 This Page Intentionally Left Blank ...
Страница 246: ...246 Part Number STH026 2 12 This Page Intentionally Left Blank ...
Страница 247: ......