COOLING TOWER APPLICATIONS
Water Cooled Models Only
A water-cooling tower installation does not require
modification of the ice machine. The water regulator
valve for the condenser continues to control the
refrigeration discharge pressure.
It is necessary to know the amount of heat rejected,
and the pressure drop through the condenser and
water valves (inlet to outlet) when using a cooling
tower on an ice machine.
Plumbing must conform to state and local codes
•
Water entering the condenser must not exceed
90°F (32.2°C).
•
Water flow through the condenser must not
exceed 5 gallons (19 liters) per minute.
•
Allow for a pressure drop of 7 psig (.48 bar)
between the condenser water inlet and the outlet
of the ice machine.
•
Water exiting the condenser must not exceed
110°F (43.3°C).
!