The voltage at the compressor during start-up is too
low.
Manitowoc ice machines are rated at ±10% of
nameplate voltage at compressor start-up. (Ex: An
ice machine rated at 208-230 should have a
compressor start-up voltage between 187 and 253
volts.)
•
The compressor discharge and suction pressures
are not matched closely enough or equalized.
These two pressures must be somewhat equalized
before attempting to start the compressor. The
harvest valve (and HPR valve on remotes)
energizes for 45 seconds before the compressor
starts, and remains on 5 seconds after the
compressor starts. Make sure this is occurring and
the harvest valve (and HPR solenoid) coil is
functional before assuming that the PTCR is bad.
CHECKING THE PTCR
1. Visually inspect the PTCR. Check for signs of
physical damage.
NOTE:
The PTCR case temperature may reach 210°F
(100°C) while the compressor is running. This is
normal. Do not change a PTCR just because it is hot.
2. Wait at least 10 minutes for the PTCR to cool to
room temperature.
3. Remove the PTCR from the ice machine.
4. Measure the resistance of the PTCR as shown on
the next page. If the resistance falls outside of the
acceptable range, replace it.
!
Warning
Disconnect electrical power to the entire ice
machine at the building electrical disconnect box
before proceeding.
Содержание Marine Q 1000
Страница 1: ... Manitowoc Ice Inc P N 80 1099 9 8 03 ...
Страница 2: ......
Страница 10: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 19: ... 9 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 20: ... 10 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 34: ... 24 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 79: ... 69 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 80: ... 70 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 114: ... 104 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 173: ... 163 SV1406 FIG A PINCHING OFF TUBING FIG B RE ROUNDING TUBING USING PINCH OFF TOOL ...
Страница 177: ......
Страница 178: ......