Working conditions

Dampers are designed for smoke exhaust piping systems with underpressure max. 1500 Pa or
overpressure max. 500 Pa.

 

Dampers are designed for maximum air velocity 12 m.s.

Dampers are installed with the horizontal or vertical axis of the blades.

 

Dampers are intended for installation on air ducts and in/onto the walls where in the case of wall

installation, this wall with damper does not have fire resistance and therefore does not separate
two fire compartments.

 

Dampers are suitable for systems without abrasive, chemical and adhesive particles.

 

Dampers are designed for macroclimatic areas with mild climate according to EN 60 72133.

 

Temperature in the place of installation is permitted to range from  - 20°C to + 50°C.

 

Design with actuating mechanism

 

SEDS-L  is  equipped  by  actuating  mechanism  Belimo  BLE24  (BE24-12)  for  24V  supply  or
BLE230  (BE230-12)  for  230V  supply.  After  being  connected  to  power  supply  the  actuating
mechanism displaces the damper blade into operation position "OPEN" or „CLOSED“ (according
to method of connection, see connection diagram). Running time is max. 60s. If is power supply
cut off, actuating mechanism is stopped in actual position. The crank handle supplied with the
actuator allows it to be operated manually. Signaling of the damper blade positions "OPEN" and
"CLOSED" is provided by means of two integrated, invariably set terminal switches.

Содержание SEDS-L

Страница 1: ......

Страница 2: ...for production designing ordering delivery maintenance and operation 1 Description 2 2 Design 3 3 Dimensions weights 8 4 Placement and Assembly 10 5 Pressure drops 12 6 Noise data 12 7 Material 14 8...

Страница 3: ...applications according with EN 1366 9 The field of direct applications based on tests results is acceptable according to EN 1363 1 part A 1 and A 2 EN 1366 2 part 13 and EN 1366 10 part 9 Smoke extrac...

Страница 4: ...r macroclimatic areas with mild climate according to EN 60 72133 Temperature in the place of installation is permitted to range from 20 C to 50 C Design with actuating mechanism SEDS L is equipped by...

Страница 5: ...II II Degree of protection IP 54 Running time for 95 30 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 80 C Connecting motor auxiliary switch cable 1 m 3 x 0 75 mm cable 1 m 6 x...

Страница 6: ...imensioning 18 VA Imax 8 2 A 5 ms 15 VA Imax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Running time for 95 60 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 8...

Страница 7: ...the BKSE24 6 unit It also receives positioning commands from the control unit and triggers the actuator to the required position The last control command is retained troughout temporary power failure...

Страница 8: ...ed by the BKSE24 6 unit and evaluated individually All BKNE230 24 units are triggered simultaneously To BKSE24 6 can be connected max 6 BKNE230 24 Communication is via the 2 wire conductor Correct ope...

Страница 9: ...consumption 3 5 W operating position Dimensioning 5 5 VA 18 VA Imax 6 4 A 2 5 ms Protection class III Degree of protection IP 20 Ambient temperature range 0 50 C Connecting screw terminals for cable 2...

Страница 10: ...BE 5 44 5 0 3075 BE 5 38 5 0 1785 BE 5 47 0 0 3485 BE 6 41 6 0 1947 BE 6 50 9 0 3801 BE 6 43 6 0 2157 BE 6 53 4 0 4211 BE 1 15 9 0 0369 BLE 1 19 2 0 0653 BLE 2 18 3 0 0439 BLE 2 22 2 0 0777 BLE 2 19...

Страница 11: ...0 4928 BE 4 63 2 0 6647 BE 4 56 7 0 5788 BE 4 67 4 0 7807 BE 5 62 5 0 6450 BE 5 74 5 0 8700 BE 5 66 0 0 7310 BE 5 78 7 0 9860 BE 6 71 8 0 7972 BE 6 85 8 1 0753 BE 6 75 4 0 8832 BE 6 90 0 1 1913 BE Smo...

Страница 12: ...11 Installation examples Pozice 1 Damper hinge 2 Nut 3 Washer 4 Profile C 5 Washer C 6 Wall construction without fire resistance...

Страница 13: ...63 68 68 67 65 62 48 57 65 70 70 69 67 64 50 w air velocity in the free cross section AxB i e before blades f frequency of octave band Sound power level corrected with filter A ps static pressure drop...

Страница 14: ...67 65 62 48 w air velocity in the free cross section AxB i e before blades f frequency of octave band 13 21 26 26 25 23 20 6 21 29 34 34 33 31 28 14 28 36 41 41 40 38 35 21 34 42 47 47 46 44 41 27 38...

Страница 15: ...re must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages when transported and manipulated All effective safety standards and directi...

Страница 16: ...case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure that the damper is put into condition in which it is ready for...

Страница 17: ...mechanism BLE24 BE24 12 54 with the communication and supply device BKNE 230 24 and actuating mechanism BLE24 BE24 12 ST 66 insulation inside of the blades I flanges with height 20 mm F WEIGHT kg Dob...

Страница 18: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...