Damper casing and damper blade are made of galvanized plate without any other surface finish.

Fasteners are galvanized.

 

The  appliance  is  constructed    and  preset  by  the  manufacturer,  its  operation  is  dependent  on
 proper installation and adjustment.

Dampers are transported by box freight vehicles without direct weather impact, there must not
occur any shocks and ambient temperature must not  40 °C. Dampers must be protected
against  mechanic  damages  when  transported  and  manipulated.  During  transportation,  the
damper blade must be in the "CLOSED" position.

Dampers are stored indoor in environment without any aggressive vapours, gases or dust. Indoor
temperature must be in the range from -5 °C to +40 °C and maximum relative humidity 80 %.
Dampers must be protected against mechanic damages when transported and manipulated.

 

All effective safety standards and directives must be observed during damper assembly.

 

To ensure reliable smoke exhaust damper function it is necessary to avoid blocking the closing
mechanism and contact surfaces with collected dust, fibre and sticky materials and solvents.

 

 Without power supply, the damper can be operated manually and fixed in any required position.

 

The actuator cover is made of fire-resistant material (fire protection board)

 

Assembly, maintenance and damper function check can be done only by qualified and trained
person, i.e. “AUTHORIZED PERSON” according to the manufacturer documentation. All works
done on the fire dampers must be done according international and local norms and laws.

Содержание SEDS-L

Страница 1: ......

Страница 2: ...for production designing ordering delivery maintenance and operation 1 Description 2 2 Design 3 3 Dimensions weights 8 4 Placement and Assembly 10 5 Pressure drops 12 6 Noise data 12 7 Material 14 8...

Страница 3: ...applications according with EN 1366 9 The field of direct applications based on tests results is acceptable according to EN 1363 1 part A 1 and A 2 EN 1366 2 part 13 and EN 1366 10 part 9 Smoke extrac...

Страница 4: ...r macroclimatic areas with mild climate according to EN 60 72133 Temperature in the place of installation is permitted to range from 20 C to 50 C Design with actuating mechanism SEDS L is equipped by...

Страница 5: ...II II Degree of protection IP 54 Running time for 95 30 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 80 C Connecting motor auxiliary switch cable 1 m 3 x 0 75 mm cable 1 m 6 x...

Страница 6: ...imensioning 18 VA Imax 8 2 A 5 ms 15 VA Imax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Running time for 95 60 s Ambient temperature range Non operating temperature 30 C 50 C 40 C 8...

Страница 7: ...the BKSE24 6 unit It also receives positioning commands from the control unit and triggers the actuator to the required position The last control command is retained troughout temporary power failure...

Страница 8: ...ed by the BKSE24 6 unit and evaluated individually All BKNE230 24 units are triggered simultaneously To BKSE24 6 can be connected max 6 BKNE230 24 Communication is via the 2 wire conductor Correct ope...

Страница 9: ...consumption 3 5 W operating position Dimensioning 5 5 VA 18 VA Imax 6 4 A 2 5 ms Protection class III Degree of protection IP 20 Ambient temperature range 0 50 C Connecting screw terminals for cable 2...

Страница 10: ...BE 5 44 5 0 3075 BE 5 38 5 0 1785 BE 5 47 0 0 3485 BE 6 41 6 0 1947 BE 6 50 9 0 3801 BE 6 43 6 0 2157 BE 6 53 4 0 4211 BE 1 15 9 0 0369 BLE 1 19 2 0 0653 BLE 2 18 3 0 0439 BLE 2 22 2 0 0777 BLE 2 19...

Страница 11: ...0 4928 BE 4 63 2 0 6647 BE 4 56 7 0 5788 BE 4 67 4 0 7807 BE 5 62 5 0 6450 BE 5 74 5 0 8700 BE 5 66 0 0 7310 BE 5 78 7 0 9860 BE 6 71 8 0 7972 BE 6 85 8 1 0753 BE 6 75 4 0 8832 BE 6 90 0 1 1913 BE Smo...

Страница 12: ...11 Installation examples Pozice 1 Damper hinge 2 Nut 3 Washer 4 Profile C 5 Washer C 6 Wall construction without fire resistance...

Страница 13: ...63 68 68 67 65 62 48 57 65 70 70 69 67 64 50 w air velocity in the free cross section AxB i e before blades f frequency of octave band Sound power level corrected with filter A ps static pressure drop...

Страница 14: ...67 65 62 48 w air velocity in the free cross section AxB i e before blades f frequency of octave band 13 21 26 26 25 23 20 6 21 29 34 34 33 31 28 14 28 36 41 41 40 38 35 21 34 42 47 47 46 44 41 27 38...

Страница 15: ...re must be in the range from 5 C to 40 C and maximum relative humidity 80 Dampers must be protected against mechanic damages when transported and manipulated All effective safety standards and directi...

Страница 16: ...case that dampers are found unable to serve for their function for any cause it must be clearly marked The operator is obliged to ensure that the damper is put into condition in which it is ready for...

Страница 17: ...mechanism BLE24 BE24 12 54 with the communication and supply device BKNE 230 24 and actuating mechanism BLE24 BE24 12 ST 66 insulation inside of the blades I flanges with height 20 mm F WEIGHT kg Dob...

Страница 18: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...