manualshive.com logo in svg
background image

Page 7

Version 2022-12-20

SEDS-L - Smoke extraction damper - single

TPM 158/22

Actuator BELIMO BE 24-12(-ST)

Actuator BELIMO BE 230-12

Actuator BELIMO BE 24-12(-ST), BE 230-12

Actuator BELIMO - 40 Nm

BE 24-12(-ST)

BE 230-12

Power voltage

AC/DC 24 V

50/60Hz

AC 230 V

50/60Hz

Power consumption - in operation
 

- in the end position

12 W

0,5 W

8 W

0,5 W

Dimensioning

18 VA (Imax 8,2 A @ 5 ms)

15 VA (Imax 7.9 A @ 5 ms)

Protection class

III

II

Degree of protection

IP 54

Adjustment time for 95°

< 60 s

Ambient temperature
Storage temperature

-30°C … +55°C
-40°C … +80°C

Connection - drive
 

- auxiliary switch

Cable 1 m, 3 x 0,75 mm

2

Cable 1 m, 6 x 0,75 mm

2

(BE 24-ST) with plug connectors

S2

S1

S3

S5

S4

S6

2

1

3

<3°

<87°

S2

S1

S3

S5

S4

S6

2

1

3

<3°

<87°

N

L1

BEL

IMO

 - 40

 N.m

Extended leads are not possible with smoke control dampers
as the belimo cabls are not fire rated to a high Field wiring must
be  brought  into  and  terminated  within  the  damper  housing.
For more detail 

→ see pages 20 to 22

, paragraph Assembly.

Содержание SEDS-L

Страница 1: ...ik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4UB United Kingdom Tel 44 117 4526376 E Mail help mandik co uk Authorized representative SEDS L Smoke extraction damper single Technical Do...

Страница 2: ...l parameters 10 Placement and Assembly 12 Installation and suspension examples 12 Duct connection 15 Accessories 16 II TECHNICAL DATA 17 Pressure loss 17 Noise data level of acoustic output corrected...

Страница 3: ...tallation on air ducts and in onto the walls where in the case of wall installation this wall with damper does not have fire resistance and therefore does not separate two fire compartments Dampers ar...

Страница 4: ...ning cable duct which passes through an opening made in the wall of the insulated cover box when installing the damper or when connecting the actuator power cable The power and control cable must be C...

Страница 5: ...ensioning 6 VA Imax 8 2 A 5 ms 6 5 VA Imax 8 2 A 5 ms 7 VA Imax 4 A 5 ms Protection class III III II Degree of protection IP 54 Adjustment time for 95 30 s Ambient temperature Storage temperature 30 C...

Страница 6: ...ion IP 54 Adjustment time for 95 60 s Ambient temperature Storage temperature 30 C 55 C 40 C 80 C Connection drive auxiliary switch Cable 1 m 3 x 0 75 mm2 Cable 1 m 6 x 0 75 mm2 BEE 24 ST with plug co...

Страница 7: ...ax 7 9 A 5 ms Protection class III II Degree of protection IP 54 Adjustment time for 95 60 s Ambient temperature Storage temperature 30 C 55 C 40 C 80 C Connection drive auxiliary switch Cable 1 m 3 x...

Страница 8: ...ol damper control panel to BS ISO 21927 9 Cable glands Comms cable Damper control module PCB mounted on plastic rail Earth stud 230v 50hz 3A fused supply by others Switches 6 core Drive open close 230...

Страница 9: ...ions Standard height of the flange 1 Damper body 2 Damper blade 3 Actuating mechanism cover Actuating mechanism V mm D mm BEN BEE 176 5 315 BE 186 5 380 BEN BEE BKNE 236 5 315 BE BKNE 251 5 380 Flange...

Страница 10: ...BEE 25 N m 800 4 30 7 0 1413 800 4 40 5 0 2759 900 5 36 5 0 1575 BELIMO BEE 25 N m 900 5 44 5 0 3075 1000 5 38 5 0 1785 1000 5 47 0 0 3485 1100 6 41 6 0 1947 1100 6 50 9 0 3801 1200 6 43 6 0 2157 1200...

Страница 11: ...1 0 1284 250 2 34 0 0 1791 300 2 29 7 0 1664 300 2 35 9 0 2321 350 2 31 4 0 2044 350 2 37 9 0 2851 400 2 33 0 0 2424 400 2 39 9 0 3381 450 3 36 8 0 2630 450 3 47 2 0 3668 BELIMO BEE 25 N m 500 3 38 4...

Страница 12: ...ontrol device all other objects must be situated at least 350 mm from the control parts of the damper During installation the damper blades must be in position CLOSED The damper body should not be def...

Страница 13: ...rnal thread and hexagon drive Without anchor With anchor Possible examples of anchoring to the ceiling construction Follow the instructions of fixing specialist or installation company Hinge plates 2x...

Страница 14: ...ed rod M8 M20 3 Support HILTI MQ 41 or MQ 41 3 or equivalent 4 Bored plate HILTI MQZ L or equivalent 5 Washer for M8 M20 6 Nut M8 M20 7 Flange of SEDS L 8 Flange of duct max 50 Dimension elements of t...

Страница 15: ...ge connection Connection to smoke extract duct 1 SEDS L 2 Connecting air duct 3 Flange of SEDS L 4 Flange of duct 5 M8 bolt assemply bolt M8x20 mm 2 pcs large washer M8 nut M8 6 Ceramic self adhesive...

Страница 16: ...n 2022 12 20 TPM 158 22 The grilles type KMM TPM 002 96 can be used to close smoke control dampers These grilles are available in all sizes of the smoke control dampers Free area value for KMM is 78 C...

Страница 17: ...100 110 120 2 3 4 5 6 7 8 9 10 11 12 B 200 400 600 800 1000 1200mm B 250mm B 300 450mm B 350 500 700 900 1100mm w m s ps Pa II TECHNICAL DATA Pressure loss Determination of pressure loss by using diag...

Страница 18: ...00 8000 Total w m s 2 15 23 28 28 27 25 22 8 34 3 24 32 37 37 36 34 31 17 43 4 31 39 44 44 43 41 38 24 50 5 36 44 49 49 48 46 43 29 55 6 41 49 54 54 53 51 48 34 60 7 45 53 58 58 57 55 52 38 64 8 48 56...

Страница 19: ...fasteners for mounting the actuator The following components including the fasteners are made from stainless steel at all times Damper body and all components permanently attached Blade s holders incl...

Страница 20: ...price of damper For unloading and further manipulation with the damper is necessary to use appropriate tooling forklifts due to damper weight Dampers are fragile Dampers are transported by box freigh...

Страница 21: ...e connector block the protection box is made of calcium silicate plates Procedure Use drill drill size acc To suit connecting cable 2 mm for seal up by mastic and make two holes It is possible to dril...

Страница 22: ...drill size acc to suit connecting cable 2 mm for seal up by mastic and make holes min pitch of the holes must be 30 mm number of holes depends on the type of control module It is possible to drill hol...

Страница 23: ...for function and meanwhile he is obliged to provide the fire protection by another appropriate way Results of regular checks imperfections found and all important facts connected with the damper funct...

Страница 24: ...54 with actuating mechanism BEN BEE SR for 24V 65 Design 65 is not available by using actuating mechanism BE Special design F flanges with height 20 mm WEIGHT kg Dob sk 550 267 24 Hostomice Czech Rep...

Страница 25: ...ual product information see www mandik co uk MAND K a s Dob sk 550 267 24 Hostomice Czech Republic Tel 420 311 706 742 E Mail mandik mandik cz Manufacturer MANDIK UK Ltd 130 Aztec West Bristol BS32 4U...

Отзывы: