SEDS-L - Smoke extraction damper - single
TPM 158/22
Actuator BELIMO BEN 24(-ST)
Actuator BELIMO BEN 24-SR
S2
S1
S3
S5
S4
S6
2
1
3
<5°
<80°
S2
S1
S3
S5
S4
S6
2
1
3
<5°
<80°
5
Y
U
DC (0)2...10 V
DC 2...10 V
Actuator BELIMO BEN 230
S2
S1
S3
S5
S4
S6
2
1
3
<5°
<80°
N
L1
Actuator BELIMO BEN 24(-ST), BEN 24-SR, BEN 230
Actuator BELIMO - 15 Nm
BEN 24(-ST)
BEN 24-SR*
BEN 230
Power voltage
AC/DC 24 V
50/60Hz
AC/DC 24 V
50/60Hz
AC 230 V
50/60Hz
Power consumption - in operation
- in the end position
3 W
0,1 W
3 W
0,3 W
4 W
0,4 W
Dimensioning
6 VA (Imax 8,2 A @ 5 ms)
6,5 VA (Imax 8.2 A @ 5 ms)
7 VA (Imax 4 A @ 5 ms)
Protection class
III
III
II
Degree of protection
IP 54
Adjustment time for 95°
< 30 s
Ambient temperature
Storage temperature
-30°C … +55°C
-40°C … +80°C
Connection - drive
- auxiliary switch
Cable 1 m, 3 x 0,75 mm
2
Cable 1 m, 6 x 0,75 mm
2
(BEN 24-ST) with plug
connectors
Cable 1 m, 4 x 0,75 mm
2
Cable 1 m, 6 x 0,75 mm
2
Cable 1 m, 3 x 0,75 mm
2
Cable 1 m, 6 x 0,75 mm
2
Extended leads are not possible with smoke control dampers
as the belimo cabls are not fire rated to a high Field wiring must
be brought into and terminated within the damper housing.
For more detail
, paragraph Assembly.
BELI
MO
- 15
N.m