EN
VULCAN REGULATOR | Instalation, operation instractions and maintenance manual
22
|
Parameter Parameter title
Factory setting
Scope of setting
P01
Control frequency
2
0 – heating only
1 – cooling only
2 – manual changing
of Heat/Cool
3 – automatic changing
of Heat/Cool
4 – heating and cooling
P02
Choice of operational
mode with left button
1
1 – AUTO/Comfort/Antifreeze
2 – Auto/Comfort/Economy/
Antifreeze
P04
Temperature display in
F or °C
0
0 – °C
1 – °F
P05
Temperature sensor
calibration
0.0 K
-3…+3 K
P06
Temperature shown on
the display
0
0 – room temperature
1 – requested temperature
P08
Requested temperature
for comfort
21 °C
5…40 °C
P09
Limitation of minimum
requested temperature
of comfort mode
5 °C
5…40 °C
P10
Limitation of maximum
requested temperature
of comfort mode
35 °C
5…40 °C
P11
Requested value for
heating under economy
mode
10 °C
Off, 5 °C
P12
Requested value for
cooling under economy
mode
30 °C
Off, 40 °C
P14
Button lock
2
0 – forbidden
1 – automatically
2 – manually
Содержание MONZUN VULCAN
Страница 2: ...CZ Copyright MAND K a s...
Страница 13: ...CZ MAND K a s Dob sk 550 267 24 Hostomice www mandik cz 13...
Страница 14: ...EN Copyright MAND K a s...
Страница 25: ...EN MAND K a s Dob sk 550 267 24 Hostomice www mandik cz 25...
Страница 26: ...DE Copyright MAND K a s...
Страница 37: ...DE MAND K a s Dob sk 550 267 24 Hostomice www mandik cz 37...
Страница 38: ...FR Copyright MAND K a s...
Страница 49: ...FR MAND K a s Dob sk 550 267 24 Hostomice www mandik cz 49...
Страница 50: ......
Страница 51: ......