7
Current Failure
15 16
K2 contact is on if all the dampers are
open
14 11
17 18
No Failure
15 16
K2 contact is on if the damper No. 1 is
open
14 12
K2 contact is on if all the dampers are
closed
14 open
BKS24-9A communication and control device is used for group control and checks of 1 to 9 fire dampers with the actuator BFL
(BFN)24-T-ST in connection with the supply and communication device BKN230-24. Signalization of the damper blade position
is individual for each damper (9 LED diodes), but the dampers can be controlled and tested only as a group. BKS24-9A is intended
for use in superordinate control system, which can display operation mode and failure reports of the connected fire dampers.
BKS24-9A receives signals from BKN230-24 through two wire cable. Proper damper operation is indicated by two light LED diodes:
Control LED "OPEN" = damper blade in emergency position OPEN
Control LED "CLOSE" = damper blade in safety position CLOSED
If the damper does not reach the required position within the preset time, the appropriate on-board FAULT LED flashes and, at
the same time, the fault contact K1 is activated (K1 is group alarm for all 9 dampers). This contact is overridden as soon the
defective damper reaches the required position. The on-board FAULT LED remains on, until the fault is reset. Auxiliary contact
K2 is provided for signaling the positions of dampers to a supreme communication controlling system. The function of the auxiliary
contact can be programmed via terminal 14 according the next table.
The BKS24-9A unit can be clipped directly onto a 35mm DIN mounting rail and external wiring is connected by two 9-pin terminal
connectors.
Functional testing can be performed by pressing the TEST pushbutton. While this button is held depressed, the dampers run to
the safe position. Any malfunctions are indicated by the internal FAULT LED´s.
1
2
3
4
5
6
7
b
a
1)
1)
2)
BAT
1) Bridge has been installed by the manufacturer. If needed, it can be
removed ad replaced with a thermoelectric starting mechanism. If
terminals 1 and 2 are not interconnected, safety function is initiated.
2) Bridge can be used only for starting and without BKS24… !
Two conductor wiring to BKS24
Содержание FDMS
Страница 1: ......
Страница 14: ...14 50 50 41 575 146 125 D D1 2 x D min 2 x D min C...
Страница 18: ...18 Fire classification 96 47 47 96 96...
Страница 21: ...21 Fire classification 96 47 47 96 96...
Страница 24: ...24 Fire classification 96 47 47 96 96...