Current Failure

15                     16

K2 contact is on if all the dampers are
open

14                     11

17                     18

No Failure

15                     16

K2 contact is on if the damper No. 1 is
open

14                     12

K2 contact is on if all the dampers are
closed

14    open

BKS24-9A communication and control device is used for group control and checks of 1 to 9 fire dampers with the actuator BFL
(BFN)24-T-ST in connection with the supply and communication device BKN230-24. Signalization of the damper blade position
is individual for each damper (9 LED diodes), but the dampers can be controlled and tested only as a group. BKS24-9A is intended
for use in superordinate control system, which can display operation mode and failure reports of the connected fire dampers.
BKS24-9A receives signals from BKN230-24 through two wire cable. Proper damper operation is indicated by two light LED diodes:

Control LED "OPEN" = damper blade in emergency position OPEN

Control LED "CLOSE" = damper blade in safety position CLOSED

If the damper does not reach the required position within the preset time, the appropriate on-board FAULT LED flashes and, at
the same time, the fault contact K1 is activated (K1 is group alarm for all 9 dampers). This contact is overridden as soon the
defective damper reaches the required position. The on-board FAULT LED remains on, until the fault is reset. Auxiliary contact
K2 is provided for signaling the positions of dampers to a supreme communication controlling system. The function of the auxiliary
contact can be programmed via terminal 14 according the next table.

The BKS24-9A unit can be clipped directly onto a 35mm DIN mounting rail and external wiring is connected by two 9-pin terminal
connectors.
Functional testing can be performed by pressing the TEST pushbutton. While this button is held depressed, the dampers run to
the safe position. Any malfunctions are indicated by the internal FAULT LED´s.

1

2

3

4

5

6

7

b

a

1)

1)

2)

BAT

1)  Bridge has been installed by the manufacturer. If needed, it can be

removed ad replaced with a thermoelectric starting mechanism. If
terminals 1 and 2 are not interconnected, safety function is initiated.

2)  Bridge can be used only for starting and without BKS24… !

Two conductor wiring to BKS24

Содержание FDMS

Страница 1: ......

Страница 2: ...n accordance with one of the following standards EN 54 5 EN 54 7 EN 54 12 or EN 54 20 The damper must be controlled by an actuator connected to a higher level supervisory and constrol system Correct o...

Страница 3: ...here must by installed inspection door externally on the duct next to the fire damper The damper is equipped with additional collar around the position of the blade On the collar there are positioned...

Страница 4: ...ible connect to the building management system or superordinate control system by wires which are mounted to the switch Design with mechanical control can be complemented with a limit switch signaling...

Страница 5: ...on OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing the damper s blade position...

Страница 6: ...ordinate system controls via the same wiring to the actuating mechanism To allow more simple connection the actuator BFL BFN 24 T ST is equipped with two connecting plugs one with three jacks and one...

Страница 7: ...sition within the preset time the appropriate on board FAULT LED flashes and at the same time the fault contact K1 is activated K1 is group alarm for all 9 dampers This contact is overridden as soon t...

Страница 8: ...8 AC 24 V 50 60Hz 3 5 W operating position 5 5 VA III safe small voltage IP 30 0 50 C Terminals for conductor 2 x 1 5 mm...

Страница 9: ...of the blade from the position OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing...

Страница 10: ...the specified field of application It may only be installed by suitably trained personnel Any legal regulations or regulations issued by authorities must be observed during assembly BU blue BN brown...

Страница 11: ...C Ri 100 k 50 k 0 4 20 mA Rext 500 0 2 10 VDC max 0 5 mA closed Vmin Vmax open normal duty storage temperature 0 C 50 C 20 C 80 C controller actuators screw terminals 4 pin 0 5 2 5 mm cable 1000 mm wi...

Страница 12: ...DM3 Actuating mechanism flow direction Controller GUAC PM3 p Pa Static pressure difference between p duct and surrounding environment s s air outlet Room Actuating mechanism Controller GUAC PM3 p Pa...

Страница 13: ...80 200 225 250 280 315 355 400 450 BFN24 T ST BFN230 T 500 560 630 98 190 113 313 405 12 70 163 123 215 113 353 445 2 32 90 163 158 250 113 398 490 24 5 54 5 112 5 163 178 270 2 5 113 448 540 49 5 79...

Страница 14: ...14 50 50 41 575 146 125 D D1 2 x D min 2 x D min C...

Страница 15: ...r and the construction wall ceiling must be minimum 75 mm In case that two or more dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers mu...

Страница 16: ...lid ceiling construction 110 Concrete 125 Aerated concrete Wet Mortar or gypsum Outside solid ceiling construction with 110 Concrete 125 Aerated concrete insulation of the pipe between wall and dam pe...

Страница 17: ...ness 1mm e g PROMASTOP P or K Fire damper FDMS Anchor for damper collar e g FISCHER type ZYKON FZA M8x30 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LG...

Страница 18: ...18 Fire classification 96 47 47 96 96...

Страница 19: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Страница 20: ...ire damper FDMS Anchor for damper collar threaded rod and nuts M8 or e g anchor FISCHER type KD8 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LGS Inspec...

Страница 21: ...21 Fire classification 96 47 47 96 96...

Страница 22: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Страница 23: ...KON FZA M8x30 Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Fire classification View A...

Страница 24: ...24 Fire classification 96 47 47 96 96...

Страница 25: ...anging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Installation of pipe insulation perform according instructions of the manufacturer This fixing p...

Страница 26: ...nd pipe only recommended Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included in supply of manufacturer Inspection hole for camera covered with removable air tigh...

Страница 27: ...ect Wired MAT 4 0 ALU1 PAROC hvac Fire Mat BlackCoat Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included i...

Страница 28: ...The insulation of the pipe must cover the damper collar from back side 1 0 10 0 100 0 10 100 1000 10000 Air flow m3 h Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 Insulation ed...

Страница 29: ...Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 30 200 200 45 310 310 55 400 400 70 500 500 90 650 650 115 800 800 145 1000 1000 180 1250 1250 220 1550 1550 280 2000 2000 355 2500...

Страница 30: ...normal 0 i 0 10 VDC invers 2 i 2 10 VDC invers Setting the nominal volumetric flow depending on the VAV box Through connecting the power supply to BU BN 1 2 and a reference signal Y to BK 3 in the ra...

Страница 31: ...43 45 2 5 15 22 28 33 37 41 44 47 49 2 2 12 20 26 32 36 40 43 46 49 2 2 6 14 21 27 32 36 39 43 46 2 2 2 6 13 19 24 28 32 36 39 2 2 2 2 2 7 13 18 22 25 29 2 2 2 5 10 13 16 19 22 24 26 2 2 9 15 20 24 27...

Страница 32: ...36 39 43 46 49 2 2 6 14 21 26 31 35 39 42 45 2 2 2 5 12 18 23 28 32 35 39 2 2 2 2 2 7 12 17 21 25 28 2 2 2 4 9 12 15 18 21 23 25 2 2 8 14 19 23 27 30 32 35 37 2 4 13 20 25 30 33 37 40 42 45 2 5 14 22...

Страница 33: ...38 42 45 48 51 2 2 8 16 23 29 34 38 41 45 48 2 2 2 8 15 21 26 30 34 38 41 2 2 2 2 3 9 15 19 24 27 31 2 2 2 8 12 16 19 22 24 26 28 2 3 11 18 23 27 30 33 36 38 40 2 7 16 23 29 33 37 40 43 46 48 2 8 18 2...

Страница 34: ...18 20 22 24 2 2 7 13 18 22 26 29 32 34 36 2 3 12 19 25 29 33 36 39 41 44 2 4 14 21 27 32 36 39 43 45 48 2 2 11 19 25 31 35 39 43 45 48 2 2 5 13 20 26 30 35 39 41 45 2 2 2 5 12 18 23 27 31 35 38 2 2 2...

Страница 35: ...for all material variants of the dampers The thermal link is identical for all material variants of the dampers Upon specification by customer the thermal link may be made from A4 from stainless steel...

Страница 36: ...after restoration of power supply e g by releasing the RESET button or restoration of supply from ELECTRICAL FIRE SIGNALISATION Without power supply the damper can be operated manually and fixed in an...

Страница 37: ...th actuator by cable With actuating mechanism BFL BFN 230 T sensor BAT is not mounted on the damper s body only connected with actuator by cable With actuating mechanism BFL BFN 24 T ST and communicat...

Страница 38: ...158 100 130 95 178 100 175 105 198 100 175 115 223 100 175 127 248 100 175 140 278 100 175 155 313 100 175 173 353 100 175 193 398 125 225 220 448 125 225 245 498 125 225 270 558 125 225 300 628 125 2...

Страница 39: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...