30
Through connecting the power supply to BU+BN (1+2) and a
reference signal Y to BK (3) in the range of (0)2…10 VDC,
the connected actuator regulates to the set point. The current
flow in % of Vnom is provided as a feedback signal U on GY
(4) for other actuators and can be communicated via PP-Bus.
CAP modes / override controls:
AC*/DC signal to terminal BK (3)
The controller is overload-proof.
The selector allows the changing of values. The position of the
arrow shows the value set. The changes are displayed as soon
as the selector is moved ±10° from the position.
Setting the desired actual volume flow unit in m³/h and l/s.
Adjust the desired flow Vmin (setpoint Y = 0 / 2 VDC).
Adjust the desired flow Vmax (setpoint Y = 10 VDC).
Diagnostic menu:
off - diagnostic mode is off
on - diagnostic mode is on
oP - opens the damper
cL - closes the damper
Lo - activated Vmin
Hi - activated Vmax
123 - software version
Setting the direction of rotation:
0-n...0-10 VDC normal
2-n...2-10 VDC normal
0-i ...0-10 VDC invers
2-i ...2-10 VDC invers
Setting the nominal volumetric flow depending on the VAV-box.
Through connecting the power supply to BU+BN (1+2) and a
reference signal Y to BK (3) in the range of (0)2…10 VDC,
the connected actuator regulates to the specified set point.
The current pressure in % of Pnom is provided as a feedback
signal U on GY (4) for other actuators and can be communi-
cated via PP-Bus.
CAP modes / override controls:
AC*/DC signal to terminal BK (3)
The controller is overload-proof.
The selector allows the changing of values. The position of the
arrow shows the value set. The changes are displayed as soon
as the selector is moved ±10° from the position.
Setting the desired actual pressure unit to Pa and H O.
Adjust the desired flow Pmin (setpoint Y = 0 / 2 VDC).
Adjust the desired flow Pmax (setpoint Y = 10 VDC).
Diagnostic menu:
off - diagnostic mode is off
on - diagnostic mode is on
oP - opens the damper
cL - closes the damper
Lo - activated Vmin
Hi - activated Vmax
123 - software version
Setting the direction of rotation:
0-n...0-10 VDC normal
2-n...2-10 VDC normal
0-i ...0-10 VDC invers
2-i ...2-10 VDC invers
Shows the nominal pressure setting.