6

AC 230 V 50/60 Hz

AC 24 V 50/60 Hz

DC 24 V

- motoring

 

- holding

3,5/5 W

1,1/2,1 W

2,5/4 W

0,8/1,4 W

6,5/10 VA (Imax 4 A @ 5 ms)

4/6 VA (Imax 8,3 A @ 5 ms)

II

III

IP 54

- motor

 

  - spring return

<60 s

~ 20 s

- normal duty

 

- safety duty

 

- non-operating temperature

- 30 °C … 55 °C

The safe position will be attained up to max. 75°C

- 40 °C … 55 °C

- motor

 

  - auxiliary switch

cable 1 m, 2 x 0,75 mm

²

  (BFL/BFN 24-T-ST) with 3-pin plug-in connectors

cable 1 m, 6 x 0,75 mm

²

  (BFL/BFN 24-T-ST) with 6-pin plug-in connectors

duct outside temperature 72 °C

duct inside temperature 72 °C

This is design with the communication and supply device BKN230-24 and the actuator BFL (BFN) 24-T-ST. It simplifies electrical wiring
and interconnection of fire damper. This design facilitates checking of the damper on site and enables central control and check of fire
damper during by a simple "2-wire" wiring with superordinate control unit. BKN230-24 is working as a decentralized network device
for supplying of the actuator BFL (BFN) 24-T-ST on one hand and on the other hand it transmits the signal information about the fire
damper  position  and  failure.  Control  command  SWITCH-ON  and  SWITCH-OFF  from  superordinate  system  controls  via  the  same
wiring to the actuating mechanism. To allow more simple connection, the actuator BFL (BFN) 24-T-ST is equipped with two connecting
plugs  (one  with  three  jacks  and  one  plug  with  six  jacks).  They  are  inserted  directly  to  BKN230-24.  BKN230-24  is  supplied  with  a
conductor and EURO-plug for connecting to the 230V mains. Two wire cable from superordinate system is connected to BKN230-24
by means of clamps 6 and 7 in BKN. If the drive is supposed to be controlled without any signal from the superordinate, it can be
switch-on by means of a bridge between clamps 3 and 4 in BKN. A green LED diode on BKN230-24 is lighting in case the voltage 24V
is present in the drive. If the TEST button on BAT is switched-on or if the power supply (e.g. by a signal from ELECTRICAL FIRE
SIGNALISATION) is disconnected, the fire damper position will be "FAILURE". It means damper blade goes in position "CLOSED".
Communication and supply device BKN230-24 has to be placed near the damper (BKN isn´t mounted on damper body). It is necessary
for easy connection of actuator equipped by BKN230-24 device.

AC 230V 50/60Hz

3,5 W (operating position)

11 VA (including actuating mechanism)

II

IP 42

- 30 °C … + 50 °C
- 40 °C … + 50 °C

- mains

 

  - drive

 

- terminal board

Cable 0,9 m with EURO plug of 26 type

6 pole plug, 3 pole plug

screw terminals for conductor 2x1,5 mm

Содержание FDMS

Страница 1: ......

Страница 2: ...n accordance with one of the following standards EN 54 5 EN 54 7 EN 54 12 or EN 54 20 The damper must be controlled by an actuator connected to a higher level supervisory and constrol system Correct o...

Страница 3: ...here must by installed inspection door externally on the duct next to the fire damper The damper is equipped with additional collar around the position of the blade On the collar there are positioned...

Страница 4: ...ible connect to the building management system or superordinate control system by wires which are mounted to the switch Design with mechanical control can be complemented with a limit switch signaling...

Страница 5: ...on OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing the damper s blade position...

Страница 6: ...ordinate system controls via the same wiring to the actuating mechanism To allow more simple connection the actuator BFL BFN 24 T ST is equipped with two connecting plugs one with three jacks and one...

Страница 7: ...sition within the preset time the appropriate on board FAULT LED flashes and at the same time the fault contact K1 is activated K1 is group alarm for all 9 dampers This contact is overridden as soon t...

Страница 8: ...8 AC 24 V 50 60Hz 3 5 W operating position 5 5 VA III safe small voltage IP 30 0 50 C Terminals for conductor 2 x 1 5 mm...

Страница 9: ...of the blade from the position OPEN to the position CLOSE takes maximal 20s In the case that the power supply is restored again the blade can be in arbitrary position the actuator starts re displacing...

Страница 10: ...the specified field of application It may only be installed by suitably trained personnel Any legal regulations or regulations issued by authorities must be observed during assembly BU blue BN brown...

Страница 11: ...C Ri 100 k 50 k 0 4 20 mA Rext 500 0 2 10 VDC max 0 5 mA closed Vmin Vmax open normal duty storage temperature 0 C 50 C 20 C 80 C controller actuators screw terminals 4 pin 0 5 2 5 mm cable 1000 mm wi...

Страница 12: ...DM3 Actuating mechanism flow direction Controller GUAC PM3 p Pa Static pressure difference between p duct and surrounding environment s s air outlet Room Actuating mechanism Controller GUAC PM3 p Pa...

Страница 13: ...80 200 225 250 280 315 355 400 450 BFN24 T ST BFN230 T 500 560 630 98 190 113 313 405 12 70 163 123 215 113 353 445 2 32 90 163 158 250 113 398 490 24 5 54 5 112 5 163 178 270 2 5 113 448 540 49 5 79...

Страница 14: ...14 50 50 41 575 146 125 D D1 2 x D min 2 x D min C...

Страница 15: ...r and the construction wall ceiling must be minimum 75 mm In case that two or more dampers are supposed to be installed in one fire separating construction the distance between the adjacent dampers mu...

Страница 16: ...lid ceiling construction 110 Concrete 125 Aerated concrete Wet Mortar or gypsum Outside solid ceiling construction with 110 Concrete 125 Aerated concrete insulation of the pipe between wall and dam pe...

Страница 17: ...ness 1mm e g PROMASTOP P or K Fire damper FDMS Anchor for damper collar e g FISCHER type ZYKON FZA M8x30 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LG...

Страница 18: ...18 Fire classification 96 47 47 96 96...

Страница 19: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Страница 20: ...ire damper FDMS Anchor for damper collar threaded rod and nuts M8 or e g anchor FISCHER type KD8 Fixing part of the pipe between wall and pipe only recommended Hanging ring e g FISCHER type LGS Inspec...

Страница 21: ...21 Fire classification 96 47 47 96 96...

Страница 22: ...00 Fire classification Connecting surface between wall and pipe insulation fulfil with fire resistant sealant before instalation of the insulation recommended type of sealant see instalation instructi...

Страница 23: ...KON FZA M8x30 Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Fire classification View A...

Страница 24: ...24 Fire classification 96 47 47 96 96...

Страница 25: ...anging ring e g FISCHER type LGS Inspection hole for camera covered with removable air tight rubber cap Installation of pipe insulation perform according instructions of the manufacturer This fixing p...

Страница 26: ...nd pipe only recommended Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included in supply of manufacturer Inspection hole for camera covered with removable air tigh...

Страница 27: ...ect Wired MAT 4 0 ALU1 PAROC hvac Fire Mat BlackCoat Fixing part of the pipe between wall and pipe optional Hanging ring e g FISCHER type LGS Permeation shielding sheet metal element is not included i...

Страница 28: ...The insulation of the pipe must cover the damper collar from back side 1 0 10 0 100 0 10 100 1000 10000 Air flow m3 h Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 Insulation ed...

Страница 29: ...Pressure drop Pa 200 14000 Air flow m3 h Pressure drop Pa 200 14000 30 200 200 45 310 310 55 400 400 70 500 500 90 650 650 115 800 800 145 1000 1000 180 1250 1250 220 1550 1550 280 2000 2000 355 2500...

Страница 30: ...normal 0 i 0 10 VDC invers 2 i 2 10 VDC invers Setting the nominal volumetric flow depending on the VAV box Through connecting the power supply to BU BN 1 2 and a reference signal Y to BK 3 in the ra...

Страница 31: ...43 45 2 5 15 22 28 33 37 41 44 47 49 2 2 12 20 26 32 36 40 43 46 49 2 2 6 14 21 27 32 36 39 43 46 2 2 2 6 13 19 24 28 32 36 39 2 2 2 2 2 7 13 18 22 25 29 2 2 2 5 10 13 16 19 22 24 26 2 2 9 15 20 24 27...

Страница 32: ...36 39 43 46 49 2 2 6 14 21 26 31 35 39 42 45 2 2 2 5 12 18 23 28 32 35 39 2 2 2 2 2 7 12 17 21 25 28 2 2 2 4 9 12 15 18 21 23 25 2 2 8 14 19 23 27 30 32 35 37 2 4 13 20 25 30 33 37 40 42 45 2 5 14 22...

Страница 33: ...38 42 45 48 51 2 2 8 16 23 29 34 38 41 45 48 2 2 2 8 15 21 26 30 34 38 41 2 2 2 2 3 9 15 19 24 27 31 2 2 2 8 12 16 19 22 24 26 28 2 3 11 18 23 27 30 33 36 38 40 2 7 16 23 29 33 37 40 43 46 48 2 8 18 2...

Страница 34: ...18 20 22 24 2 2 7 13 18 22 26 29 32 34 36 2 3 12 19 25 29 33 36 39 41 44 2 4 14 21 27 32 36 39 43 45 48 2 2 11 19 25 31 35 39 43 45 48 2 2 5 13 20 26 30 35 39 41 45 2 2 2 5 12 18 23 27 31 35 38 2 2 2...

Страница 35: ...for all material variants of the dampers The thermal link is identical for all material variants of the dampers Upon specification by customer the thermal link may be made from A4 from stainless steel...

Страница 36: ...after restoration of power supply e g by releasing the RESET button or restoration of supply from ELECTRICAL FIRE SIGNALISATION Without power supply the damper can be operated manually and fixed in an...

Страница 37: ...th actuator by cable With actuating mechanism BFL BFN 230 T sensor BAT is not mounted on the damper s body only connected with actuator by cable With actuating mechanism BFL BFN 24 T ST and communicat...

Страница 38: ...158 100 130 95 178 100 175 105 198 100 175 115 223 100 175 127 248 100 175 140 278 100 175 155 313 100 175 173 353 100 175 193 398 125 225 220 448 125 225 245 498 125 225 270 558 125 225 300 628 125 2...

Страница 39: ...reserves the right for innovations of the product For actual product information see www mandik com MAND K a s Dob sk 550 26724 Hostomice Czech Republic Tel 420 311 706 706 E Mail mandik mandik cz ww...