background image

Sealed Systems

A sealed system should follow the guidelines given
in the Code of Practice BS 7074 :1.  It should
include a safety valve to BS 6750 Pt 1. fitted close
to the boiler, without an intermediate valve to the
system and in a position where it can be tested. It
should be preset to operate at 3 bar (45 lb/in²) and
sited to discharge through a pipe to a safe outlet.

An expansion vessel complying with BS 4814 must
be fitted to the system close to the return side of the
pump. The connection should be not less than
15mm and without a valve or restriction. Size the
vessel by using the table below.

1. Choose a vessel pressure by taking the static

head of the system, adding 0.3 bar, and taking
the nearest larger size.

2. Select the Vessel Volume from the table below

by finding the system volume and vessel pres-
sure.

3. Choose that size or larger from the

manufacturers’ range.

Vessel

System Volume 

Litres

Pressure

50

60

70

100

150

Bar

Vessel Volume

0.5

4

4

8

8

12

1.0

8

8

8

12

18

1.5

8

12

12

18

24

A pressure gauge with a fill pressure indicator and a
range of 0-4 bar should be fitted close to the expan-
sion vessel in a visible position.

A design as detailed below should be used for the
filling connection, it utilises a BS 1010 stop valve, a
double non-return valve and filling loop  fitted at low
level and should be installed with the approval of the
local Water Undertaking.

Electricity Supply

Refer to Figs. 3 and 4.

Wiring external to the appliance MUST be in accord-
ance with the current I.E.E. Wiring Regulations and
any Local Regulations that apply.

The boiler is supplied for 230V ~ 50Hz. Single
phase. Fuse rating is 3A.

The method of connection to the mains electricity
supply MUST facilitate complete electrical isolation
of the boiler, preferably by the use of a fused double
pole switch having a 3mm (1/8in.) contact separa-
tion in both poles and servicing only the boiler and
system controls.

The point of connection to the mains should be
readily accessible and adjacent to the boiler, except
that, for bathroom installations, the point of connec-
tion to the mains MUST be situated outside the
bathroom.

Note.

 Where a room sealed appliance is installed in

a room containing a bath or shower, the appliance,
any electrical switch or appliance control utilising
mains electricity should be so situated that it cannot
be touched by a person using the bath or shower.

Installation Of Boiler

Suggested procedure:

1. Site to suit system and terminal limitations.

2. Mark Boiler Mounting Box fixing position. (Fig.

5).

3. Mark & Drill Flue hole(s).

(see Fig. 7 for Concentric, Fig. 8 for Twin Pipe).

4. Fix Boiler Mounting Box to the wall.

5. Remove the Electrical tray and the Case from

boiler module.

6. Plumb module for water and gas OFF the wall

(access is much better).

7. Fix the Boiler to its Mounting Box.

8. Plumb tails to system and gas.

9. Test for leaks.

10. Replace the Case and Electrical tray.

Space Required for Installation and Service.

Right or Left

30 mm

1¼ in.

Above

30mm

1¼ in.

Below

25mm

1 in.

In Front

450mm

18 in.

Condensing Boiler

     

5

           03/09/02

ALTERNATIVE METHODS OF FILLING A SEALED
SYSTEM

Method A

Method B

Hose Unions

Air Inlet

Valve

Temporary Hose

Mains
Water

Supply

Mains
Water

Supply

Test Cock

Stop Valve

Drain &
Fill

Double
Check
Valve
Assembly

Drain &

Fill

Cistern &
Overflow

Pressure
Pump &
Reducing
Valve If
Required

Stop Valve

Содержание tentwenty

Страница 1: ...1 555 18 41 555 19 Serial Number 0087 tentwenty twentytwentysix Condensing Boilers Installation Service Instructions Note to the Installer Natural and Propane Gas Please leave these Instructions adjac...

Страница 2: ...P 20 kg 28 kg 1 4 litres 3 bar 1 m 30 82 C 10 12 litres m 5 litres m 22mm Copper 230V 50Hz 40W 1 Amp 20mm 3 Amp 790 High 400 Wide 330 Deep 450 Front 30 Above 25 Below 30 Left Right Concentric 160 High...

Страница 3: ...s may require the addition of a bypass an automatic bypass is preferred The boilers also contain integral frost protection the boiler will fire if the temperature within it approaches 4 to 5 degrees C...

Страница 4: ...he purpose Details of essential features of cupboard compartment design including airing cupboard installations are given in BS 6798 In siting the boiler the following limitations MUST be observed 1 T...

Страница 5: ...ter system if applicable should be in accordance with the relevant recommenda tions of BS 5546 Copper tubing to BS 2871 1 is recommended for water carrying pipework The hot water storage cylinder MUST...

Страница 6: ...The boiler is supplied for 230V 50Hz Single phase Fuse rating is 3A The method of connection to the mains electricity supply MUST facilitate complete electrical isolation of the boiler preferably by t...

Страница 7: ...cut off during installation Right or Left Outlet 1 Secure the 50mm flue tube with ELBOW connec tor on the saddle using the Velcro strap See Fig 7 2 Measure carefully and saw off the 50mm tube to give...

Страница 8: ...and Side Trim 3 With the bottom of the boiler away from the wall hang the top of the back panel onto the Mounting Box Now by gently lowering the bottom of the boiler against the wall the fan spigot sh...

Страница 9: ...minimum flow conditions An automatic bypass is preferred The boiler waterside is completely copper so all good corrosion inhibitors are suitable Designs The following designs are all acceptable 1 Seal...

Страница 10: ...pletely normal It is recommended that the gas cock is turned off during this early stage Because of a built in delay the boiler is always held off for a minimum of 120 seconds However for commissionin...

Страница 11: ...em hot check again for water sound ness Refit the case to the boiler Add remainder of corrosion inhibitor Balance the system in the normal way to obtain even heating of all radiators If fitted set the...

Страница 12: ...fill system adding 3 4 of the inhibitor Do not light boiler Vent all radiator and air release points Run pump for 5 10 second bursts and revent Condensing Boiler 11 06 06 01 Do not light boiler Run pu...

Страница 13: ...ngths Minimum 200mm Maximum 22m horizontal 90mm 90 bend 4 0m 45 bend 1 3m Suggested core drill Suggested core drill 128mm Flue 100 to 2000mm Left right or rear Flue Air Concentric Flues Service Access...

Страница 14: ...NSOR 12 Way connector GV1 GV2 N 4 Core to Gas Valve Fan 4 way Molex 10 way Molex GV1 GV2 1 Amp 20mm CONTROL BOARD Or Or Br Br R W Bk Gy Br R Bk Br G G Y G Y G Y B G Y V Gy Br R Or W Bk Gy V G Y B Brow...

Страница 15: ...Condensing Boiler 14 06 06 01 Physical Wiring Diagram Fig 4...

Страница 16: ...Wall Fixing Holes 2 Lower Wall Fixing Holes Core Drill 128mm 118 Use 2 at the top and any other 2 below 236 288 167 92 32 17 kW For Concentric 270 For Twin Pipe Core Drill 90 mm Condensing Boiler 15...

Страница 17: ...1 Boiler Panel Assembly Control Board Chassis Electrical Cover Top Trim Front Burner Baffle Side Trim Fig 6 Pressure Cover Concentric Flue Boiler Mounting Box Fan Protection Hoop Lower Burner Baffle T...

Страница 18: ...e Positions Fig 7 Fig 8 Flue Duct Air Duct 100mm Condensate Drain Connection connects to drain point on Flue Spigot Adapter Flue Spigot Adapter Drain Point Twin Pipe Boiler Mounting Box Assembly Conne...

Страница 19: ...me is detected and the control board stops sparking and then energises the main gas valve and the burner lamp is illuminated The pilot flame lights the burner and it stays alight until turned off by t...

Страница 20: ...Condensing Boiler 19 03 07 03 Fault Diagnosis...

Страница 21: ...quired If in doubt drain the system and remove for inspection 2 Condensate Syphon With a suitable bowl to catch the water un screw the drain cap s on the underside of the Syphon trap and drain the wat...

Страница 22: ...NCE CASE COULD RESULT IN LEAKAGE OF COMBUSTION PRODUCTS INTO THE ROOM 3 Fan Assembly Lower the Electrical Tray Remove the Case Undo the wing nut holding the Fan Protec tion Hoop Pull the electrical co...

Страница 23: ...ove the Case Pull off the HT lead from the Control board Undo the left and right screws holding the Front Burner Baffle Remove the front baffle Release the tube nut holding the electrode to the Pilot...

Страница 24: ...04 Fan Assembly 17 kW M1095 Fan Assembly 24 kW M0910 106 435 Control Board M3752 Control Assembly M3915 Gas Valve Sigma 840 M3783 Air Pressure Switch Concentric Flues 7712 379 091 Air Pressure Switch...

Страница 25: ...ces Flue Thermostat Fan Assembly Secondary Heat Exchanger Fibre Washer 2 Places Flow Pipe Control Sensor O H Stat Primary Heat Exchanger Gas Manifold HT Lead Pilot Assembly Main Injector Electrode Pil...

Страница 26: ...Trap Air Gap Air Gap 110mm Soil Pipe or Drain Soakaway Insulate against freezing 150mm Land Drain Filled with Gravel 750mm deep Condensate Drain from Boiler Air Pressure Switch pipe connection Vent Sy...

Страница 27: ...e specification without notice Your statutory rights are not affected Malvern Boilers Ltd Enigma Business Park Spring Lane Malvern WORCS WR14 1BW Telephone 01684 893777 Fax 01684 893776 www malvernboi...

Отзывы: