Hearth dimensions shown are minimum requirements.  It may be desired to exceede these minimum dimensions
for a more decorative installation.

SIDEWALL AND BACKWALL INSTALLATION

Unit to Sidewall ----------------------------------------- 42"
Unit to Backwall ---------------------------------------- 42"
Connector to Sidewall -------------------------------- 58"
Center of Connector to Sidewall ------------------- 63"
Connector to Backwall ------------------------------- 58"
Center of connector to Backwall ------------------- 63"

58"

42"

42"

58"

Figure 2.

Figure 1.

CORNER INSTALLATION

Unit to Adjacent Walll --------------------------------- 42"
Connector to Adjacent Wall ------------------------- 58"
Center of Connector to Adjacent Wall ------------ 63"
Minimum Hearth Size ------------------------- 48" x 54"
Or a Diameter of --------------------------------------- 54"

Chimney System

Connector Pipe

Unit

Clearance to Combustibles

The Imperial requires a clearance to combustible walls of 42"
measured from the back of the unit.  For locating the center of
the chimney the measurement is 63" from the backwall and 63"
to the sidewall.  See figure 1, page 2.  For corner installation the
center of the chimney is 63".  See figure 2, page 2.

Clearance to Non-combustibles

The Imperial clearance to a combustible  wall may be reduced
with  proper  wall  protection.        Accepted  methods  for  wall
protection would allow reduction of the wall clearances.  For
appearance  if  desired  a  non-combustible  wall  covering  can
placed on the wall.  The covering should consist of a  listed wall
protection board installed to the manufacturer's specifications.
Approved protection boards at the time of this publication are
Wonderboard, Dura Rock and Homosote.  A non-combustible
material can then be placed over the wall protection board.  With
most of the protection boards the clearance can be reducedby
2/3  from the original combustible wall.  Be certain to check with
your local building officials and or fire inspector for accepted
methods in your area.

Содержание Imperial Carousel

Страница 1: ...is necessary to get a somewhat dry mixture to much water in the mix may cause the refractory to crack exces sively and will reduce the strength of the refractory To test for proper water content cut vertically into the mixture with the trowel push the trowel sideways to open a 3 inch deep by 2 inch wide cut in the mixture then slide the trowel back up out of the cut The cut should stay open with v...

Страница 2: ...terialon one edge These pieces go on either side of thedoor Makecertainthatthesetwopieces are placed completly into the channel on either side of the door Failure to do this will maketherestoftheglassinstallationimpos sible 7 First loosen the glass retainers This is a metal strip secured by one screw in the middle Start with the left door panel The gasketmustbeontherightsideofthepanel 8 Slide the ...

Страница 3: ...e chimney the measurement is 63 from the backwall and 63 to the sidewall See figure 1 page 2 For corner installation the center of the chimney is 63 See figure 2 page 2 Clearance to Non combustibles The Imperial clearance to a combustible wall may be reduced with proper wall protection Accepted methods for wall protection would allow reduction of the wall clearances For appearance if desired a non...

Страница 4: ...48 54 16 Figure 3 54 Diameter Circle Hearth 8 Minimum is measured from the fire box 8 8 8 16 From Door Simpson Dura Vent Chimney System It is required to use a Dura Vent Universal Connector part number 8874 to install the chimney connector 1 The universal connector is installed into the support box The 8 x 30 slip pipe is then connected to the universal connector 2 The 8 x 30 starter pipe section ...

Страница 5: ...tion method of installing the connector pipe with the male end down allows for any moisture to remain on the inside of the connector pipe IMPORTANT THE SINGLE WALLCONNECTOR PIPE MUST NEVER PASS THROUGH A COMBUSTIBLE CEILING OR WALL At first glance you may become concerned that smoke will escape the pipe and enter the room This is not how the system will work The vacum in the chimney system will al...

Страница 6: ...gns of deterioration It is best to have the chimney inspected by a professional Make certain the chimney is cleaned prior to installation of this fireplace The size of the chimney should be between 36 and 96 square inches Larger chimneys should be relined to meet these requirements Incorrect sizing of the chimney may affect the draft and result in poor fireplace performance Do not install more tha...

Страница 7: ...g when using this or any other wood burning appli ance A partially open window or outside air register in the vicinity of the unit would be accept able Combustion air must be supplied in con formance with the Uniform Mechanical Code Imperial Carousel Page 7 7 CAUTION NEVERUSEGASOLINE GASOLINE TYPE LANTERN FUEL KEROSENE CHAR COAL LIGHTER FLUID OR SIMILAR LIQUIDS TO START OR FRESHEN UP A FIRE IN THI...

Страница 8: ...ote has accumulated it should be removed to reduce the chance of a chimney fire HOW TO REMOVE CREOSOTE 1 Clean the chimney with brushes and equipment available at local fireplace shops 2 Chemical chimney cleaners are used by adding them to the fire but they are not intended for use in chimneys already containing heavy soot deposits Rather they are intended to inhibit soot buildup They can be used ...

Отзывы: