4 Detailed Functions Description
Allow timer reset?
Defines if the delay time is reset when a
Start message arrives.
Possible values:
*No
Yes
Timer expiration Pre-Warning
usage
Defines how the timer expiration warning
shall be issued.
Possible values:
Not used
Send Message via Pre-Warning CO
*Invert output (during 1s)
Send M Invert output
Timer expiration pre-warning
The amount of time before timer
expiration that the warning must be
issued.
Possible values:
*15s, 30s, … 2min, 5min, 10min, …
20min
Pre-warning message type
Defines the type of message to send via
“Pre-Warning”
CO.
Possible values:
*On
Off
Timer Delay change via Com.
Obj.
Defines if the timer's delay time can be
changed via communication object, and
which is the Datapoint Type of the CO.
Possible values:
*Not used
DPT7.005 TimePeriodSec
(PDTUNSIGNED_INT)
DPT9.010 TimeValue
(PDT_KNX_FLOAT)
Time Limited Toggle Switch
Defines the delay time for the switch-Off
when using the
“Time Limited
Toggle Switch”
CO.
Possible values:
1s, 2s, [+1s]… *10s, ... 1min, 1min
15s, [+15s] …. 2min, 3min,
[+1min]… 15min, 20min,
[+15min]… 1h, 2h, [+1h]…
1day
“On/Off” Com.Obj. Function
Defines the behaviour of the device upon
messages on the
“On / Off”
CO.
Possible values:
*On / Off
Delayed On (immediate Off)
Delayed Off (immediate On)
Delayed On / Off
Timer On
Timer Off
On Delay amount
Defines the amount of delay to apply
between “On” message arrival and
switching the channel.
Possible values:
1s, 2s, [+1s]… *10s, ... 1min, 1min
15s, [+15s] …. 2min, 3min,
[+1min]… 15min, 20min,
[+15min]… 1h, 2h, [+1h]…
1day
Off Delay amount
Defines the amount of delay to apply
between “Off” message arrival and
switching the channel.
Possible values:
1s, 2s, [+1s]… *10s, ... 1min, 1min
15s, [+15s] …. 2min, 3min,
[+1min]… 15min, 20min,
[+15min]… 1h, 2h, [+1h]…
1day
8
Visible if
“Timer Pre-Warning expiration usage”
is set to value different than “Not used”.
9
Visible if
“Timer Pre-Warning expiration usage”
is set to “Send Message via Pre-Warning CO” or “
Send
M Invert output
”
10 The operation of
Time Limited Toggle Switch
is not affected by the previous parameters.
11 Visible if
“''On/Off'' Com.Obj. Function”
set to “Delayed On (immediate Off)” or “Delayed On/Off”.
12 Visible if
“''On/Off'' Com.Obj. Function”
set to “Delayed Off (immediate On)” or “Delayed On/Off”.
User’s Manual
Page 17
Содержание MSA-CM Series
Страница 5: ...1 GENERAL INFORMATION User s Manual Page 5...
Страница 7: ...2 SYSTEM SUMMARY User s Manual Page 7...
Страница 10: ...3 GETTING STARTED User s Manual Page 10...
Страница 12: ...4 DETAILED FUNCTIONS DESCRIPTION User s Manual Page 12...
Страница 32: ...4 Detailed Functions Description User s Manual Page 32 Figure 11 Usage of Slat Angle Stop Up Down CO...
Страница 39: ...Appendixes APPENDIXES User s Manual...